| 2017-03-30 11:14:55 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1. DETAIL 1-S5.001, OTHER LOCATIONS, STRUCTURAL |
| | SHEATHING SHOWN. REVISE PLAN TO SHOW COMPLIANCE WITH |
| | FBC B 603.1 (COMBUSTIBLES ALLOWED). |
| | |
| | 2. G2.001 DOES NOT ADDRESS THE SMOKE CONTROL AND/OR |
| | ELEVATOR PRESSURIZATION. NO ELEVATOR LOBBIES ARE SHOWN |
| | AS EXISTING OR PROPOSED AND AN ATRIUM IS SHOWN. REVISE |
| | PLAN TO ADDRESS (FUNCTIONAL EXISTING SYSTEMS TO |
| | REMAIN?) |
| | |
| | 3. G2.001 STATES THAT EXISTING OCCUPANT LOAD IS "TO |
| | REMAIN." PROVIDE THE OCCUPANT LOAD, FBC 107. THIS |
| | INFORMATION IS REQUIRED FOR C.O., COMPLIANCE WITH FBC |
| | EB 805, FBC B CHAPTER 10. |
| | |
| | 4. 01-G2.001 SHOWS (EXISTING) EXITING THROUGH A LOADING |
| | ZONE. FBC 107, CODE COMPLIANCE SHOULD BE CLEAR TO |
| | SOMEONE UNFAMILIAR WITH THE BUILDNG. ALTHOUGH |
| | "EXISTING", IT IS NOT CLEAR WHETHER EXITING THROUGH A |
| | MORE HAZARDOUS AREA WAS ALLOWED WHEN THE BUILDING WAS |
| | PERMITTED. REVISE PLAN TO CLARIFY. INCLUDE A NORTH |
| | ARROW. IT IS NOT CLEAR IF THIS IS THE ALLEY OR ANOTHER |
| | AREA WHICH IS NOT VISIBLE ON PICTOMETRY AND OTHER |
| | AERIALS. |
| | |
| | 5. S0.00 RAILINGS, REVISE DESIGN CRITERIA TO INCLUDE |
| | ALL REQUIREMENTS OF FBC B 1607.8. |
| | |
| | 6. THIS PERMIT WILL BE ISSUED WITH PROVISO, ENGINEERING |
| | AND SHOP DRAWINGS FOR RAILINGS REQUIRED AT INSPECTION. |
| | SUBJECT TO INSPECTOR'S DISCRETION, THIS MAY BE REQUIRED |
| | TO BE SUBMITTED FOR PLAN REVIEW. DOR TO REVIEW |
| | DELEGATED ENGINEERING AND SHOPS PRIOR TO INSPECTION |
| | AND/OR SUBMITTAL. |
| | |