| Plan Review Notes For Permit 17030908 |
| Permit Number |
17030908 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-04-17 13:28:42 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1.THE WATER CLOSET AND SHOWER ARE NOT VENTED ON RISER | | | DIAGRAM. PER FBC PL P3101.2.1 | | | | | | 2. SHT. S-2 SHOWS A WATER RISER WITH A TANKLESS WATER | | | HEATER AND A NEW WATER PIPING ISO WITH AN EXISTING TANK | | | TYPE WATER HEATER PLEASE CLARIFY. PER WPB AMEND TO FBC | | | 107.2.1 | | | | | | | | | FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT | | | THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL | | | COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|