| Notes |
| Date |
Text |
| 2017-07-17 10:42:44 | 4TH REVIEW FBC-2014 MECHANICAL | | | PERMIT #17030764 | | | 7/17/17 | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE CORRECTED AC PLANS INDICATE THEY WERE DRAWN BY | | | THE COMPANY THAT PREPARED THE AC CALCULATIONS- ENERGY | | | HOUSE TECHNOLOGY. PLEASE NOTE THAT ENERGY HOUSE | | | TECHNOLOGY CANNOT DRAW THE AC PLAN FOR THE HOUSE UNLESS | | | THE COMPANY IS FL. STATE LICENSED AS AN AC OR | | | MECHANICAL CONTRACTOR, AND IS THE INSTALLING CONTRACTOR | | | ON THE PROJECT- SECTION 105.3.1 WEST PALM BEACH | | | AMENDMENTS TO THE FBC. I PERFORMED A LICENSE SEARCH ON | | | THE DPBR WEBSITE AND NO CONTRACTORS LICENSE EXISTS FOR | | | EITHER ENERGY HOUSE TECHNOLOGY OR THE COMPANY OWNER | | | BRUCE TSCHOSIK. | | | | | | 2) PLEASE PROVIDE DUPLICATE COPIES OF THE AC | | | CALCULATIONS FOR LEVELS 1 & 2- ONLY ONE SET WAS | | | SUBMITTED. | | | | | | 3) THE SUBMITTAL FOR THE HURRICANE PAD INDICATES AN | | | INCORRECT WIND SPEED OF 150 MPH WHICH IS DEFICIENT FOR | | | WEST PALM BEACH THE CORRECT ULTIMATE DESIGN WIND SPEED | | | FOR RISK CATEGORY II STRUCTURES IN WPB IS 170 MPH- | | | SECTION 1609 FBC-14 BUILDING. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|