| Plan Review Notes For Permit 17030764 |
| Permit Number |
17030764 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-23 09:49:16 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17030764 | | | 3/23/17 | | | | | | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | | NEW MINI-SPLIT SYSTEM- SECTION R403.6.1 FBC-14 ENERGY | | | CONSERVATION. | | | | | | 2) REFER TO SECTION R101.4.5 FBC-14 ENERGY | | | CONSERVATION: THE PBC PROPERTY APPRAISOR'S REPORT FOR | | | THE EXISTING RESIDENCE INDICATES BUILDING 2 HAS NO | | | HEATING OR AIR CONDITIONING, THEREFORE NOW THAT IT IS | | | BEING CONDITIONED, FULL COMPLIANCE WITH THE ENERGY CODE | | | IS REQUIRED. PLEASE SUBMIT COMPLIANCE DOCUMENTATION AS | | | OUTLINED IN SECTIONS R101.5.1.1. | | | | | | 3) PROVIDE A PLAN THAT SHOWS THE LOCATIONS OF THE NEW | | | AIR HANDLER AND EXTERIOR CONDENSER, AND PROVIDE AN AC | | | EQUIPMENT SCHEDULE. | | | | | | 4) REMOVE THE AC CHANGE-OUT FORM FROM THE PERMIT FILE- | | | IT IS NOT APPLICABLE TO THIS PROJECT. | | | | | | 5) PROVIDE A CONDENSATE DISPOSAL PLAN FOR THE AIR | | | HANDLER- SECTION M1411.3 FBC-14 RESIDENTIAL. | | | | | | 6) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF THE | | | CONDENSER PAD AND MOUNTING DETAILS FOR THE CONDENSER- | | | SECTION M1305.1.4.1. | | | | | | 7) PROVIDE ELECTRICAL PLANS. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|