| Plan Review Notes For Permit 17030730 |
| Permit Number |
17030730 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-27 16:10:48 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | GAS COMMENTS: | | | | | | 1. SHOW THE DISTANCE FROM THE POINT OF DELIVERY, | | | (METER), TO THE MOST REMOTE OUTLET IN THE BUILDING | | | AND/OR SYSTEM PER THE FBC-2014 FUEL GAS APPENDIX A ? | | | USE OF CAPACITY SECTION A.3.1(4) & 2014 FUEL GAS CODE | | | SEC. 402.4.1. | | | | | | 2. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS ALL | | | NEW CUT SECTIONS OF PIPE AND CORRESPONDING LENGTHS PER | | | FBC-2014 FUEL GAS, SECS. 402.4.1, 402.4.2. | | | | | | 3. SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL | | | PIPE SIZES, AND THE EHD NUMBER OF CORRUGATED STAINLESS | | | STEEL TUBING FOR EACH PIPE SIZE IF BEING USED. WPB | | | AMENDMENTS TO FBC SEC. 107.2.1. | | | | | | 4. SHOW BTU LOAD OF EACH APPLIANCE AND THE TOTAL BTU | | | LOAD ON THE SYSTEM. REFER TO THE FBC-2014 FUEL GAS | | | SECS. 401.8 THRU 402.6.1 AND TABLES 402.4(1) THRU | | | 402.4(37). | | | | | | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|