| Notes |
| Date |
Text |
| 2017-03-21 12:03:09 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | THE PLAN DOES NOT INDICATE THE SIZE OR WIRING METHOD | | | FOR THE NEW CIRCUITS. RECEPTACLES IN THE KITCHEN FOR | | | THE COUNTER TOP SHALL BE SERVED BY A MINIMUM OF TWO 20 | | | AMPERE BRANCH CIRCUITS. THE CIRCUIT SIZE FOR THE | | | REFRIGERATOR AND MICRO WAS NOT SPECIFIED. FBC E3901.3, | | | E3901.4 | | | | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND | | | OUTSIDE EACH SLEEPING AREA. A BUILDING WITH GAS | | | APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE IS | | | REQUIRED TO HAVE A CARBON MONOXIDE DETECTOR WITHIN TEN | | | FEET OF EACH ROOM USED FOR SLEEPING. FBC R314, 315 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6654(OFFICE) | | | 561-373-3701(CELL) | | | | | | | | | |
|