2017-03-21 12:03:09PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 THE PLAN DOES NOT INDICATE THE SIZE OR WIRING METHOD
 FOR THE NEW CIRCUITS. RECEPTACLES IN THE KITCHEN FOR
 THE COUNTER TOP SHALL BE SERVED BY A MINIMUM OF TWO 20
 AMPERE BRANCH CIRCUITS. THE CIRCUIT SIZE FOR THE
 REFRIGERATOR AND MICRO WAS NOT SPECIFIED. FBC E3901.3,
 E3901.4
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. A BUILDING WITH GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE IS
 REQUIRED TO HAVE A CARBON MONOXIDE DETECTOR WITHIN TEN
 FEET OF EACH ROOM USED FOR SLEEPING. FBC R314, 315
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER