| 2017-03-28 08:50:42 | 1ST REVIEW FBC-2014 MECHANICAL |
| | PERMIT #17030708 |
| | 3/28/17 |
| | |
| | 1) SHEET 3.0: PLEASE IDENTIFY ALL ROOMS AND SPACES ON |
| | THE FLOOR PLANS- SECTION 107.2.1 WPB AMENDMENTS TO THE |
| | FBC. |
| | |
| | 2) ENERGYGAUGE FORM R405-2014: |
| | |
| | A) THE IDENTIFICATIONS OF THE APARTMENTS ON THE FORMS |
| | (A, B ETC.) DO NOT MATCH THE PLANS WHICH LISTS THE |
| | UNITS NUMERICALLY. PLEASE CORRELATE THE PLANS AND |
| | CALCULATIONS SO THEY MATCH. |
| | |
| | B) THE FORMS ARE LACKING COMPLETE PROJECT INFORMATION |
| | AND DATA AT THE TOP OF THE FORM AND ARE NOT SIGNED BY |
| | THE OWNER/AGENT. |
| | |
| | C) THE FORMS ARE INDICATING A "WORST CASE" COMPLIANCE |
| | WHICH IS ONLY PERMITTED FOR MODEL HOME COMPLIANCE- SEE |
| | SECTION R405.4.2 EXCEPTION. |
| | |
| | D) THE CHECKLISTS HAVE NOT BEEN COMPLETED. |
| | |
| | 4) SHEET 3.0: PROVIDE THE EQUIPMENT SCHEDULES FOR AHU'S |
| | # 2 & 3. PLEASE NOTE ENERGYGAUGE FORM R405 AND THE AC |
| | CALCULATIONS EACH LIST THE SYSTEMS AS 16 SEER. |
| | |
| | 5) 3.0, 1ST FLOOR APT: |
| | |
| | A) PROVIDE THE SIZE OF THE BEDROOM/HALLWAY TRANSFER |
| | DUCT. |
| | |
| | B) CLARIFY IF AHU-3 HAS AN OPEN RETURN BECAUSE THE |
| | D/600 RETURN GRILL IS UNDERSIZED. |
| | |
| | 6) 3.0: 2ND FLOOR: |
| | |
| | A) PROVIDE THE FLEX DUCT SIZES, |
| | |
| | B) THE BEDOOM TRANSFERS ARE MISLABELED AS SUPPLY |
| | DIFFUSERS AND ARE UNDERSIZED- 50 SQ. INCHES PER 100 |
| | CFMS REQUIRED. ONE BEDROOM TRANSFER IN UNIT 201 IS NOT |
| | LABELED. |
| | |
| | C) INDICATE WHICH TYPE OF BI-FOLD DOORS ARE ENCLOSING |
| | THE AHU CLOSETS. |
| | |
| | 7) PROVIDE KITCHEN AND BATH EXHAUST SYSTEMS IN |
| | ACCORDANCE WITH TABLE M1507.4 FBC-14 RESIDENTIAL. SEE |
| | ALSO SECTION R303.3 FOR BATHROOM VENTILATION IF USING |
| | AN OPERABLE WINDOW. |
| | |
| | CHRISTOPHER L. COLE |
| | MECHANICAL PLANS EXAMINER |