2017-03-28 08:50:421ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17030708
 3/28/17
  
 1) SHEET 3.0: PLEASE IDENTIFY ALL ROOMS AND SPACES ON
 THE FLOOR PLANS- SECTION 107.2.1 WPB AMENDMENTS TO THE
 FBC.
  
 2) ENERGYGAUGE FORM R405-2014:
  
 A) THE IDENTIFICATIONS OF THE APARTMENTS ON THE FORMS
 (A, B ETC.) DO NOT MATCH THE PLANS WHICH LISTS THE
 UNITS NUMERICALLY. PLEASE CORRELATE THE PLANS AND
 CALCULATIONS SO THEY MATCH.
  
 B) THE FORMS ARE LACKING COMPLETE PROJECT INFORMATION
 AND DATA AT THE TOP OF THE FORM AND ARE NOT SIGNED BY
 THE OWNER/AGENT.
  
 C) THE FORMS ARE INDICATING A "WORST CASE" COMPLIANCE
 WHICH IS ONLY PERMITTED FOR MODEL HOME COMPLIANCE- SEE
 SECTION R405.4.2 EXCEPTION.
  
 D) THE CHECKLISTS HAVE NOT BEEN COMPLETED.
  
 4) SHEET 3.0: PROVIDE THE EQUIPMENT SCHEDULES FOR AHU'S
 # 2 & 3. PLEASE NOTE ENERGYGAUGE FORM R405 AND THE AC
 CALCULATIONS EACH LIST THE SYSTEMS AS 16 SEER.
  
 5) 3.0, 1ST FLOOR APT:
  
 A) PROVIDE THE SIZE OF THE BEDROOM/HALLWAY TRANSFER
 DUCT.
  
 B) CLARIFY IF AHU-3 HAS AN OPEN RETURN BECAUSE THE
 D/600 RETURN GRILL IS UNDERSIZED.
  
 6) 3.0: 2ND FLOOR:
  
 A) PROVIDE THE FLEX DUCT SIZES,
  
 B) THE BEDOOM TRANSFERS ARE MISLABELED AS SUPPLY
 DIFFUSERS AND ARE UNDERSIZED- 50 SQ. INCHES PER 100
 CFMS REQUIRED. ONE BEDROOM TRANSFER IN UNIT 201 IS NOT
 LABELED.
  
 C) INDICATE WHICH TYPE OF BI-FOLD DOORS ARE ENCLOSING
 THE AHU CLOSETS.
  
 7) PROVIDE KITCHEN AND BATH EXHAUST SYSTEMS IN
 ACCORDANCE WITH TABLE M1507.4 FBC-14 RESIDENTIAL. SEE
 ALSO SECTION R303.3 FOR BATHROOM VENTILATION IF USING
 AN OPERABLE WINDOW.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER