Plan Review Notes
Plan Review Notes For Permit 17030708
Permit Number 17030708
Review Stop E
Sequence Number 1
Notes
Date Text
2017-03-23 14:33:03 
 17030708
 801 DOBBINS STREET
 APARTMENT REMODEL
  
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 THE PLANS AS SUBMITTED ARE DEFICIENT OR MISSING
 INFORMATION IN THE FOLLOWING AREAS.
  
 LOCATION OF PANEL BOARDS, AIR CONDITIONING EQUIPMENT,
 DISCONNECTS, TAMPER RESISTANT RECEPTACLES, MISSING
 RECEPTACLES, INTERCONNECTION OF SMOKE DETECTORS, ARC
 FAULT RECEPTACLES ARE REQUIRED THROUGHOUT, REQUIRED
 LAUNDRY CIRCUITS, SPECIFICATIONS FOR CEILING FIXTURES,
 ENERGY EFFICIENCY SPECS FOR LAMPS, HOUSE PANEL
 DIRECTORY, SERVICE LOCATION, SERVICE RISER HEIGHT,
 SERVICE DROP HEIGHT, WIRE SIZES FOR SERVICE, WIRE SIZES
 FOR WATER HEATERS, WIRE SIZES FOR PANELS, MAIN
 DISCONNECTS, INTERSYSTEM GROUNDING BAR, SERVICE FAULT
 CURRENT CALCULATIONS, PANEL BOARD FAULT CURRENT
 CALCULATIONS, ARC FAULT SAFETY LABELING, APARTMENT LOAD
 CALCULATION.
  
 NOTE THAT AIR CONDITIONING, HEATING, LAUNDRY, RANGE AND
 DRYER LOADS WERE NOT INCLUDED IN THE LOAD CALCULATIONS
 AND NEED TO BE ADDED IF THEY WILL BE PART OF THIS
 SUBMITTAL.
  
 NEC CODE SECTIONS: 210.12, 110.9, 110.10, 406.11,
 250.94, 210.52 (F), 410.116, 110.26,
  
 FBC CODE SECTIONS: E3902.12, E3609, E3703.3, ER404.1,
 E4004.8
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER