| 2017-03-23 14:33:03 | | | | 17030708 | | | 801 DOBBINS STREET | | | APARTMENT REMODEL | | | | | | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | THE PLANS AS SUBMITTED ARE DEFICIENT OR MISSING | | | INFORMATION IN THE FOLLOWING AREAS. | | | | | | LOCATION OF PANEL BOARDS, AIR CONDITIONING EQUIPMENT, | | | DISCONNECTS, TAMPER RESISTANT RECEPTACLES, MISSING | | | RECEPTACLES, INTERCONNECTION OF SMOKE DETECTORS, ARC | | | FAULT RECEPTACLES ARE REQUIRED THROUGHOUT, REQUIRED | | | LAUNDRY CIRCUITS, SPECIFICATIONS FOR CEILING FIXTURES, | | | ENERGY EFFICIENCY SPECS FOR LAMPS, HOUSE PANEL | | | DIRECTORY, SERVICE LOCATION, SERVICE RISER HEIGHT, | | | SERVICE DROP HEIGHT, WIRE SIZES FOR SERVICE, WIRE SIZES | | | FOR WATER HEATERS, WIRE SIZES FOR PANELS, MAIN | | | DISCONNECTS, INTERSYSTEM GROUNDING BAR, SERVICE FAULT | | | CURRENT CALCULATIONS, PANEL BOARD FAULT CURRENT | | | CALCULATIONS, ARC FAULT SAFETY LABELING, APARTMENT LOAD | | | CALCULATION. | | | | | | NOTE THAT AIR CONDITIONING, HEATING, LAUNDRY, RANGE AND | | | DRYER LOADS WERE NOT INCLUDED IN THE LOAD CALCULATIONS | | | AND NEED TO BE ADDED IF THEY WILL BE PART OF THIS | | | SUBMITTAL. | | | | | | NEC CODE SECTIONS: 210.12, 110.9, 110.10, 406.11, | | | 250.94, 210.52 (F), 410.116, 110.26, | | | | | | FBC CODE SECTIONS: E3902.12, E3609, E3703.3, ER404.1, | | | E4004.8 | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6654(OFFICE) | | | 561-373-3701(CELL) | | | |
|