| Plan Review Notes For Permit 17030698 |
| Permit Number |
17030698 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-23 15:12:54 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17030698 | | | 3/23/17 | | | | | | 1) SHEET M: INDICATE THE DISCHARGE HEIGHT OF THE GREASE | | | EXHAUST OUTLET MEASURED FROM THE ROOF SURFACE- SECTION | | | 506.3.13.1. | | | | | | 2) PROVIDE A GUARD AT THE ROOF EDGE BY THE EXHAUST FAN | | | IN COMPLIANCE WITH SECTION 304.11. | | | | | | 3) PROVIDE AN AIR VELOCITY CALCULATION FOR THE GREASE | | | EXHAUST DUCT- SECTION 506.3.4. | | | | | | 4) REFER TO SECTION 508.1.1: THE TEMPERATURE | | | DIFFERENTIAL BETWEEN MAKEUP AIR AND THE AIR IN THE | | | CONDITIONED SPACE SHALL NOT EXCEED 10 DEGREES F. THIS | | | TYPICALLY REQUIRES THE INSTALLATION OF A AC SYSTEM TO | | | PROVIDE THE SUPPLY AIR. | | | | | | 5) THE COPIED PLAN SHEET FROM THE MAIN PERMIT MUST BE | | | NOTED TO BE "FOR REFERENCE ONLY" BY THE ENGINEER OF | | | RECORD, OR PROVIDE A NEW REVISED SHEET WITH AN ORIGINAL | | | SEAL AND SIGNATURE BY THE ENGINEER. PLEASE NOTE THAT | | | THE WIDTH DIMENSION OF THE HOOD ON THE PLAN DOES NOT | | | MATCH THE WITH DIMENSION ON SHEET M. | | | | | | 6) PROVIDE THE OWNER INFORMATION, THE PROJECT NAME, AND | | | PCN ON THE PERMIT APPLICATION. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|