2017-03-23 15:12:541ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17030698
 3/23/17
  
 1) SHEET M: INDICATE THE DISCHARGE HEIGHT OF THE GREASE
 EXHAUST OUTLET MEASURED FROM THE ROOF SURFACE- SECTION
 506.3.13.1.
  
 2) PROVIDE A GUARD AT THE ROOF EDGE BY THE EXHAUST FAN
 IN COMPLIANCE WITH SECTION 304.11.
  
 3) PROVIDE AN AIR VELOCITY CALCULATION FOR THE GREASE
 EXHAUST DUCT- SECTION 506.3.4.
  
 4) REFER TO SECTION 508.1.1: THE TEMPERATURE
 DIFFERENTIAL BETWEEN MAKEUP AIR AND THE AIR IN THE
 CONDITIONED SPACE SHALL NOT EXCEED 10 DEGREES F. THIS
 TYPICALLY REQUIRES THE INSTALLATION OF A AC SYSTEM TO
 PROVIDE THE SUPPLY AIR.
  
 5) THE COPIED PLAN SHEET FROM THE MAIN PERMIT MUST BE
 NOTED TO BE "FOR REFERENCE ONLY" BY THE ENGINEER OF
 RECORD, OR PROVIDE A NEW REVISED SHEET WITH AN ORIGINAL
 SEAL AND SIGNATURE BY THE ENGINEER. PLEASE NOTE THAT
 THE WIDTH DIMENSION OF THE HOOD ON THE PLAN DOES NOT
 MATCH THE WITH DIMENSION ON SHEET M.
  
 6) PROVIDE THE OWNER INFORMATION, THE PROJECT NAME, AND
 PCN ON THE PERMIT APPLICATION.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  