2017-03-20 17:01:37THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1)
 SHEET A 0.0 - THERE IS A NEW DOOR PROPOSED IN THE
 CORRIDOR. IT APPEARS THAT THIS SECTION OF THE HOSPITAL
 MAY BE WITHIN AN EXISITNG SMOKE BARRIER. DOES THIS
 PROSED DOOR CONFLICT WITH THE ORIGINAL SMOKE BARRIER
 REQUIREMENTS AND/OR AFFECT ANY SMIOKE REMOVAL
 CALCULATION AIR REQUIRERMENETS.
  
 DOES THIS DOOR NEED ANY SPECIAL SEALING AND OR
 HARDWARE?
  
 PLEASE PROVIDE A REVEIW AND/ OR CHANGE..
  
  
  
 2)
 SHEET A 1.0 - DOOR # 2 DOES NOT SHOW ANY HARDWARE OR
 LOCKING EQUIPMENT. THIS DOOR IS PROPOSED IN AN EXIT
 CORRIDOR. WHAT OCCUPANY NUMBER DOES IT SERVE? IS EXIT
 OR PANIC HARDWARE REQUIRED? DOES IT LOCK OR LATCH? DOES
 IT HAVE A KEY OR THUMB LOCKING BOLT?
  
 PLEASE PROVIDE APPLICABLE EXIT EQUIPMENT.
  
  
  
 3)
 SHEET A 1.0 - DOOR # 1 DOES NOT SHOW ANY HARDWARE OR
 LOCKING EQUIPMENT. WILL THIS DOOR BE LOCKABLE? THE LOCK
 MUST MEET THE REQUIREMENTS OF NFPA 101, CHAPTER 7,
 MENAS OF EGRESS AND CAN NOT BE LOCK IN THE PATH OF
 EGRESS UNLESS MEETING THOSE REQUIREMENTS.
  
 PLEASE PROVIDE A REVIEW AND/OR CHANGE
  
  
  
 4)
 SHEET A 1.0 & E 0.1 - THE PROPOSED DOOR IN THE CORRIDOR
 IS NOT SHOWN WITH AN EXIT LIGHT LEADING TO THE EXIT.
  
 PLEASE REIVEW AND PROVIDE FOR THE APPLICABLE EXIT
 SIGNAGE.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  