| Date |
Text |
| 2017-03-18 03:15:52 | 1) ONE OF THE SUBMITTED DRAWINGS IS DONE IN PENCIL. |
| | DRAWINGS DONE IN PENCIL ARE NOT ACCEPTABLE BY THE |
| | BUILDING DIVISION AS THE MEDIUM IS NOT PERMANENT. I |
| | PERSONALLY HAVE BROUGHT THE ISSUE OF PENCILED DRAWINGS |
| | TO THE ATTENTION OF YOUR OFFICE STAFF TOO MANY TIMES |
| | AND IT IS STILL OCCURRING. COPIES WILL NOT BE MADE HERE |
| | AND THE DRAWING WILL BE REJECTED FOR THIS VERY ISSUE SO |
| | IT WOULD BENEFIT ALL INVOLVED IF YOUR OFFICE STAFF IS |
| | REMINDED OF THIS AND FOLLOW PROTOCOL. |
| | 2) PLACE A NOTE ON THE PLANS THAT THE SLAB REPAIR WILL |
| | BE DONE BY OTHERS UNDER A SEPARATE PERMIT. THE PLUMBING |
| | PERMIT WILL NOT BE FINALED UNTIL A BUILDING PERMIT |
| | APPLICATION IS SUBMITTED ALONG WITH A SLAB REPAIR |
| | DETAIL AND THE PERMIT IS ISSUED. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | 3) SUBMIT MANUFACTURER'S SPECIFICATIONS AND |
| | INSTALLATION MANUAL FOR THE PEDICURE CHAIRS.WPB AMEND. |
| | TO FBC SEC. 107.2.1. |
| | 4) THE REPLACEMENT OF THE SHOWER VALVE SHALL COMPLY |
| | WITH 2014 FBC-PLUMBING SEC.424.3. |
| | 5) IDENTIFY THE TYPE OF FIXTURES ON THE FLOOR PLAN AND |
| | THE SANITARY RISER.WPB AMEND. TO FBC SEC. 107.2.1. |
| | 6) THE SOIL SHALL BE TREATED WITH A TERMITICIDE AFTER |
| | THE PIPE INSTALLATION AND BACKFILLING IS COMPLETE. 2014 |
| | FBC-BUILDING SEC. 1816.1. A CERTIFICATE FROM THE |
| | COMPANY WHO APPLIED THE CHEMICALS SHALL BE ON THE |
| | JOBSITE CONFIRMING THE TERMITICIDE HAS BEEN APPLIED. |
| | 7) SIZE ALL SECTIONS OF THE PIPE ON THE SANITARY RISER. |
| | WPB AMEND TO FBC SEC. 107.2.1. |
| | 8) SUBMIT A WATER RISER DIAGRAM FOR REVIEW. WPB AMEND. |
| | TO FBC SEC. 107.2.1, 107.3.5.1.3. |
| | 9) WHAT TYPE OF BUSINESS WAS PREVIOUSLY IN THIS SPACE? |
| | IS THERE CURRENTLY AN ACTIVE BUSINESS IN THIS SPACE AND |
| | IF SO WHAT IS IT? THERE IS A POSSIBILITY THIS COULD BE |
| | A CHANG OF OCCUPANCY AND THE PLANS ARE TOO VAGUE TO |
| | MAKE AN EVALUATION. |
| | |
| | DUE TO THE LACK OF INFORMATION ON THE SUBMITTAL AND |
| | PLANS A THOROUGH AND COMPREHENSIVE PLAN REVIEW COULD |
| | NOT BE PERFORMED AND ADDITIONAL REVIEW COMMENTS MAY BE |
| | GENERATED ON THE RESUBMITTAL. |
| | |