| Plan Review Notes For Permit 17030670 |
| Permit Number |
17030670 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-04-26 10:35:46 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17030438 | | | 4/26/17 | | | | | | 1) THE 3.8 KW HEATING CAPACITIES IN AHU'S- 1 & 2 ARE | | | UNDERSIZED PER THE NEW SUBMITTED AC COOLING AND HEATING | | | CALCULATIONS- SECTION C403.2.2 FBC-14 ENERGY | | | CONSERVATION. A MINIMUM OF 6 AND 7.5 KW HEATERS ARE | | | REQUIRED. | | | | | | 2) SHEET M-1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE | | | RETURN AIR SYSTEMS OF THE NEW AHU'S. PROVIDE SYMBOLS ON | | | THE PLAN TO SHOW THE LOCATIONS OF THE DEVICES, AND | | | INDICATE HOW THEY WILL BE SUPERVISED- SEE SECTIONS | | | 606.2.1, AND 606.4.1 FBC-14 MECHANICAL. | | | | | | 3) M-1: PROVIDE THE CLEARANCE DISTANCE MEASUREMENTS FOR | | | THE O/A INTAKES AS OUTLINED IN SECTION 401.4, AND FOR | | | THE EXHAUST OUTLETS AS OUTLINED IN SECTION 501.3.1. | | | | | | 4) SUBMIT TWO COPIES OF THE MIAMI- DADE NOA FOR THE O/A | | | LOUVERS. | | | | | | 5) PLASE ATTACH THE MEP PLAN SETS TO THE MAIN | | | ARCHITECTURAL PLANS. FAILURE TO RETURN TWO COMPLETE, | | | CORRECTED, AND COLLATED SETS OF PLANS WILL RESULT IN A | | | FAILED PLAN REVIEW. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|