Plan Review Notes
Plan Review Notes For Permit 17030654
Permit Number 17030654
Review Stop E
Sequence Number 2
Notes
Date Text
2017-06-01 14:40:07 
 PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS AS WELL.
  
 REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO
 INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND
 OUTSIDE EACH SLEEPING AREA. IF THE BUILDING HAS GAS
 APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE, A CARBON
 MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH
 ROOM USED FOR SLEEPING. 2014 FBC R314, 315
  
 HIGH HAT CEILING LIGHTING FIXTURES IN INSULATED SPACES
 NEED TO BE RATED FOR INSULATION CONTACT (IC). FBC
 E4004.8
  
 A MINIMUM OF 75% OF THE LAMPS IN PERMANENTLY INSTALLED
 LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS OR A
 MINIMUM OF 75% OF THE PERMANENTLY INSTALLED LIGHTING
 FIXTURES SHALL CONTAIN HIGH EFFICIENCY LAMPS. FBC
 ER404.1
  
 THE PLANS DO NOT INDICATE THE SIZE OR WIRING METHOD FOR
 THE NEW CIRCUITS. RECEPTACLES IN THE KITCHEN FOR THE
 COUNTER TOP SHALL BE SERVED BY A MINIMUM OF TWO 20
 AMPERE BRANCH CIRCUITS. FBC E3901.3, E3901.4
  
 INCLUDE A PANEL SCHEDULE SHOWING THE NEW CIRCUITS WITH
 APPROPRIATE OVERCURRENT PROTECTION. NEC 110.26, FBC R
 E3405.1, E3706.2
  
 ALL NEW CIRCUITS MUST BE PROTECTED WITH ARC FAULT
 CIRCUIT BREAKERS. FBC E3902.12, NEC 210.12
  
 NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.2;
 FBC R E4002.14
  
 AN INTERSYSTEM BONDING SYSTEM IS REQUIRED AT THE
 SERVICE GROUNDING SYSTEM. FBC E3609.3
  
 GFCI PROTECTED RECEPTACLES ARE REQUIRED AT THE FRONT
 AND REAR ELEVATIONS. FBC E3902,NEC 210.8
  
 RECEPTACLES LOCATED AT THE KITCHEN ISLAND COUNTER
 REQUIRE GFCI PROTECTION. FBC E3902 NEC 210.8
  
 PROVIDE AN ELECTRICAL PLAN FOR THE RECONFIGURED LOGGIA.
 RECEPTACLES ARE REQUIRED SO THAT AT NO POINT ALONG THE
 FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A RECEPTACLE
 OUTLET AND AT WALL SPACES 2 FEET OR MORE IN WIDTH. NEC
 210.52, FBC E3901.3
  
 NOTE: THE PLANS ON SHEET A-OO2 INDICATE THE REMOVAL OF
 APPLIANCES IN THE GARAGE. THESE APPLIANCES ARE STILL
 SHOWN IN THE GARAGE ON THE ELECTRICAL PLANS. PLEASE
 CLARIFY.
  
  
 ROBERT LECKY
 ELECTRICAL PLANS EXAMINER