| 2017-06-01 14:40:07 | |
| | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING |
| | ELECTRICAL REVIEW COMMENTS AS WELL. |
| | |
| | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO |
| | INCLUDE INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND |
| | OUTSIDE EACH SLEEPING AREA. IF THE BUILDING HAS GAS |
| | APPLIANCES, AN ATTACHED GARAGE OR A FIREPLACE, A CARBON |
| | MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH |
| | ROOM USED FOR SLEEPING. 2014 FBC R314, 315 |
| | |
| | HIGH HAT CEILING LIGHTING FIXTURES IN INSULATED SPACES |
| | NEED TO BE RATED FOR INSULATION CONTACT (IC). FBC |
| | E4004.8 |
| | |
| | A MINIMUM OF 75% OF THE LAMPS IN PERMANENTLY INSTALLED |
| | LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS OR A |
| | MINIMUM OF 75% OF THE PERMANENTLY INSTALLED LIGHTING |
| | FIXTURES SHALL CONTAIN HIGH EFFICIENCY LAMPS. FBC |
| | ER404.1 |
| | |
| | THE PLANS DO NOT INDICATE THE SIZE OR WIRING METHOD FOR |
| | THE NEW CIRCUITS. RECEPTACLES IN THE KITCHEN FOR THE |
| | COUNTER TOP SHALL BE SERVED BY A MINIMUM OF TWO 20 |
| | AMPERE BRANCH CIRCUITS. FBC E3901.3, E3901.4 |
| | |
| | INCLUDE A PANEL SCHEDULE SHOWING THE NEW CIRCUITS WITH |
| | APPROPRIATE OVERCURRENT PROTECTION. NEC 110.26, FBC R |
| | E3405.1, E3706.2 |
| | |
| | ALL NEW CIRCUITS MUST BE PROTECTED WITH ARC FAULT |
| | CIRCUIT BREAKERS. FBC E3902.12, NEC 210.12 |
| | |
| | NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC 406.2; |
| | FBC R E4002.14 |
| | |
| | AN INTERSYSTEM BONDING SYSTEM IS REQUIRED AT THE |
| | SERVICE GROUNDING SYSTEM. FBC E3609.3 |
| | |
| | GFCI PROTECTED RECEPTACLES ARE REQUIRED AT THE FRONT |
| | AND REAR ELEVATIONS. FBC E3902,NEC 210.8 |
| | |
| | RECEPTACLES LOCATED AT THE KITCHEN ISLAND COUNTER |
| | REQUIRE GFCI PROTECTION. FBC E3902 NEC 210.8 |
| | |
| | PROVIDE AN ELECTRICAL PLAN FOR THE RECONFIGURED LOGGIA. |
| | RECEPTACLES ARE REQUIRED SO THAT AT NO POINT ALONG THE |
| | FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A RECEPTACLE |
| | OUTLET AND AT WALL SPACES 2 FEET OR MORE IN WIDTH. NEC |
| | 210.52, FBC E3901.3 |
| | |
| | NOTE: THE PLANS ON SHEET A-OO2 INDICATE THE REMOVAL OF |
| | APPLIANCES IN THE GARAGE. THESE APPLIANCES ARE STILL |
| | SHOWN IN THE GARAGE ON THE ELECTRICAL PLANS. PLEASE |
| | CLARIFY. |
| | |
| | |
| | ROBERT LECKY |
| | ELECTRICAL PLANS EXAMINER |