| Plan Review Notes For Permit 17030654 |
| Permit Number |
17030654 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-23 11:05:26 | PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING | | | ELECTRICAL REVIEW COMMENTS. | | | | | | PROVIDE AN ELECTRICAL PLAN FOR THE RECONFIGURED LOGGIA. | | | FBC E3901.3 | | | | | | VERIFY THAT THE EXISTING BEDROOMS HAVE THE REQUIRED | | | SMOKE AND CARBON MONOXIDE DETECTORS. REMODELING OF AN | | | EXISTING STRUCTURE IS REQUIRED TO INCLUDE | | | INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND OUTSIDE | | | EACH SLEEPING AREA. IF THE BUILDING HAS GAS APPLIANCES, | | | AN ATTACHED GARAGE OR A FIREPLACE, A CARBON MONOXIDE | | | DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH ROOM USED | | | FOR SLEEPING. 2014 FBC R314, 315 | | | | | | HIGH HAT CEILING LIGHTING FIXTURES IN INSULATED SPACES | | | NEED TO BE RATED FOR INSULATION CONTACT (IC). FBC | | | E4004.8 | | | | | | A MINIMUM OF 75% OF THE LAMPS IN PERMANENTLY INSTALLED | | | LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS OR A | | | MINIMUM OF 75% OF THE PERMANENTLY INSTALLED LIGHTING | | | FIXTURES SHALL CONTAIN HIGH EFFICIENCY LAMPS. FBC | | | ER404.1 | | | | | | | | | ROBERT LECKY | | | ELECTRICAL PLANS EXAMINER | | | 561-805-6654(OFFICE) | | | 561-373-3701(CELL) | | | | | | | | | |
|