2017-03-23 11:05:26PLEASE REVISE THE PLANS IN RESPONSE TO THE FOLLOWING
 ELECTRICAL REVIEW COMMENTS.
  
 PROVIDE AN ELECTRICAL PLAN FOR THE RECONFIGURED LOGGIA.
 FBC E3901.3
  
 VERIFY THAT THE EXISTING BEDROOMS HAVE THE REQUIRED
 SMOKE AND CARBON MONOXIDE DETECTORS. REMODELING OF AN
 EXISTING STRUCTURE IS REQUIRED TO INCLUDE
 INTERCONNECTED SMOKE ALARMS BOTH WITHIN AND OUTSIDE
 EACH SLEEPING AREA. IF THE BUILDING HAS GAS APPLIANCES,
 AN ATTACHED GARAGE OR A FIREPLACE, A CARBON MONOXIDE
 DETECTOR IS REQUIRED WITHIN TEN FEET OF EACH ROOM USED
 FOR SLEEPING. 2014 FBC R314, 315
  
 HIGH HAT CEILING LIGHTING FIXTURES IN INSULATED SPACES
 NEED TO BE RATED FOR INSULATION CONTACT (IC). FBC
 E4004.8
  
 A MINIMUM OF 75% OF THE LAMPS IN PERMANENTLY INSTALLED
 LIGHTING FIXTURES SHALL BE HIGH-EFFICACY LAMPS OR A
 MINIMUM OF 75% OF THE PERMANENTLY INSTALLED LIGHTING
 FIXTURES SHALL CONTAIN HIGH EFFICIENCY LAMPS. FBC
 ER404.1
  
  