| Date |
Text |
| 2017-06-02 10:24:25 | BUILDING PLAN REVIEW |
| | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| | ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. SUB-SURFACE INVISTEGATION BY SOILPROBE ENGINEERING & |
| | TESTING, INC. SPECIFIES THE INSTALLATION OF PIN PILES |
| | AND HELICAL-PIERS WITH A SPACING OF NOT GREATER THAN 8 |
| | FEET ON CENTER. ( SEE PAGES 3 & 4 OF REPORT AND PLAN |
| | PAGE S1.0) PLEASE CLARIFY. |
| | 2. PLAN PAGE A-002 SPECIFIES THE REMOVAL OF AN INTERIOR |
| | LOAD BEARING WALL. PLAN PAGE S2.0 SPECIFIES THIS WALL |
| | TO REMAIN. IF BEARING WALL IS TO BE REMOVED, PROVIDE |
| | SHORING DETAIL. PLEASE CLARIFY. |
| | 3. PROVIDE LINTEL/BEAM SCHEDULE. |
| | 4. PROVIDE WINDOW AND DOOR SCHEDULE WITH ROUGH OPENINGS |
| | AND DESIGN WIND LOADS. |
| | 5. DETAIL 2, PAGE S0.1 IS NOT APPLICABLE TO THIS |
| | PROJECT. NEW ROOF CONSISTS OF 2X10 P.T 16 INCHES ON |
| | CENTER. |
| | 6. PROVIDE DETAIL OF VERTICAL RE-INFORCING FOR 8" CMU |
| | IN-FILL. |
| | 7. PROVIDE DETAIL FOR THE REMOVAL OF FRENCH DOORS AND |
| | INSTALLATION OF DOUBLE WINDOWS. |
| | 8. NO MECHANICAL PLAN SUBMITTED. CANNOT VERIFY IF THERE |
| | WILL BE ADDITIONAL CONDITIONED SPACE. |
| | 9. PLAN PAGE A-007 TO BE SIGNED AND SEALED BY DESIGNER |
| | OF RECORD. |
| | |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | PLANS THAT HAVE BEEN PREPARED BY AN ENGINEER AND |
| | SUBMITTED FOR PUBLIC RECORD SHALL BEAR THE SIGNATURE, |
| | DATE AND SEAL OF THE ENGINEER PER FL ADMIN. CODE RULE |
| | 61G15-23.001. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED AND MARK VOID. |
| | |
| | |