| Plan Review Notes For Permit 17030653 |
| Permit Number |
17030653 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-20 09:38:53 | PLEASE PROVIDE MANUF. DATA SHEETS FOR NEW TANKLESS | | | HEATER TO VERIFY LOADS. FBC 107.3.5 | | | | | | SEE CALCULATIONS SUBMITTED CALLS OUT 12KW FOR TANKLESS | | | NOT 18KW AS SHOWN ON PLANS. DISCONNECT TO BE SHOWN AND | | | PROVIDED AT TANKLESS LOCATION. | | | | | | V. PEREZ | | | *6717 |
|