| Plan Review Notes For Permit 17030604 |
| Permit Number |
17030604 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-04-10 13:37:30 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | | | | 1) | | | GENERAL COMMNET - THERE ARE NO REVISION CLOUDS OR OTHER | | | INDICATIONS SHOWING WHAT OR WHERE CHANGES WERE MADE. | | | | | | 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION | | | DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND | | | SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE | | | CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD | | | CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS. | | | | | | PLEASE PROVIDE SPECIFIC INDICATORS FOR EACH AREA OF | | | REVISION ON EACH PLAN SHEET AS APPLICABLE. | | | | | | | | | | | | | | | 2) | | | SHEET A 3 - THE FIRE WALL IS INDICATED AS CALL=OUT WT2. | | | WT2 DOES NOT HAVE A FIRE WALL LISTING. | | | | | | PLEASE PROVIDE THE APPLICABLE FIRE WALL LISTING | | | REFERENCE. | | | | | | | | | | | | 3) ADDRESS OTHER CITY DEPARTMENT'S COMMENTS. | | | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | | | | |
|