Plan Review Notes
Plan Review Notes For Permit 17030604
Permit Number 17030604
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2017-04-10 13:37:30THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1)
 GENERAL COMMNET - THERE ARE NO REVISION CLOUDS OR OTHER
 INDICATIONS SHOWING WHAT OR WHERE CHANGES WERE MADE.
  
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE
 CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD
 CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS.
  
 PLEASE PROVIDE SPECIFIC INDICATORS FOR EACH AREA OF
 REVISION ON EACH PLAN SHEET AS APPLICABLE.
  
  
  
  
 2)
 SHEET A 3 - THE FIRE WALL IS INDICATED AS CALL=OUT WT2.
 WT2 DOES NOT HAVE A FIRE WALL LISTING.
  
 PLEASE PROVIDE THE APPLICABLE FIRE WALL LISTING
 REFERENCE.
  
  
  
 3) ADDRESS OTHER CITY DEPARTMENT'S COMMENTS.
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  