| 2017-03-15 08:03:33 | UPDATED 4/26/17 CT |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| | ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | FAILED AS FOLLOWS: |
| | |
| | THE RECORD INDICATES 25 WINDOWS & DOORS AND STORM |
| | PANELS WERE PERMITTED AND PARTIALLY INSTALLED PURSUANT |
| | TO 04080618, BUT THE INSPECTION FAILED AND THE PERMIT |
| | EXPIRED FOR LACK OF PRODUCT APPROVALS AND THE STORM |
| | PANELS NOT BEING INSTALLED. THE APPLICANT HAS SUBMITTED |
| | FOR REVIEW, WINDOW AND DOOR PRODUCTS FROM THE RECORD |
| | RETRIEVED FROM RECORDS STORAGE, FILENET, AND NEW |
| | PRODUCT APPROVALS FOR STORM PANELS AS NONE WERE EVER |
| | INSTALLED. THE PERMIT DESCRIPTION REFLECTS THIS. |
| | |
| | ADDRESS THE FOLLOWING COMMENTS AND RE-SUBMIT |
| | |
| | 1. THE VALUATION APPEARS LOW. THE PERMIT VALUATION AND |
| | PERMIT FEE MUST BE COMMENSURATE WITH THE VALUATION AND |
| | FEE THAT A LICENSED CONTRACTOR WOULD PROVIDE. |
| | PLEASE INCREASE THE VALUATION ACCORDINGLY. |
| | YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE |
| | OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT |
| | RENTAL TO VERIFY VALUE. |
| | 2. CONTRIBUTING HISTORIC PROPERTY. ADDRESS HISTORIC |
| | COMMENTS. |
| | |
| | |
| | THIS SUBMITTAL SHALL BE SPLIT - THE BELOW WORK SHALL BE |
| | ON SEPERATE PERMIT 4/26/17 CT |
| | |
| | ADDITIONALLY, THERE IS A LETTER INCLUDED ATTESTING THAT |
| | NO WORK WAS DONE ON EXPIRED APPLICATION 13010325. THAT |
| | APPLICATION WAS VAGUE AND THEREFORE NEVER APPROVED. |
| | THERE WAS TO BE $10,000.00 OF DRYWALL, PAINTING AND |
| | BASEBOARD WORK PERFORMED. THIS SUBMITTAL SHOULD OFFER A |
| | REPORT OF INSPECTION BY A RESPONSIBLE PERSON, |
| | CONTRACTOR OR ENGINEER, WITH AN EVALUATION OF THE |
| | APPLICATION AND THE BUILDING REGARDING THE FACTS OF THE |
| | MATTER OF 13010325 AND IT SHOULD INCLUDE REFERENCE TO |
| | CODE CASE CE13010208 WHICH CITED VIOLATIONS THAT MAY BE |
| | RELATED. |
| | |
| | FBC-107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL |
| | INFORMATION, DRAWINGS, SPECIFICATIONS AND ACCOMPANYING |
| | DATA SHALL BEAR THE NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR THE DESIGN. |
| | |
| | FBC107.1 GENERAL. SUBMITTAL DOCUMENTS CONSISTING OF |
| | CONSTRUCTION DOCUMENTS, STATEMENT OF SPECIAL |
| | INSPECTIONS, GEOTECHNICAL REPORT AND OTHER DATA SHALL |
| | BE SUBMITTED IN TWO OR MORE SETS WITH EACH PERMIT |
| | APPLICATION. |
| | |
| | FBC 109.3 BUILDING PERMIT VALUATION. FOR PERMITTING |
| | PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS SHALL BE |
| | TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND |
| | SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM |
| | OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS, |
| | WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE |
| | TECHNICAL CODES. |
| | |
| | FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR |
| | TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE |
| | TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN |
| | APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY. |
| | |