| Plan Review Notes For Permit 17030473 |
| Permit Number |
17030473 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-15 12:58:11 | INITIAL PLAN REVIEW ELECTRICAL 3/15/2017 | | | | | | 105 EVERNIA ST. BOAT SHOW 2017 | | | PERMIT 17030473 | | | | | | | | | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION | | | | | | | | | COMMENTS: | | | | | | 1. PROVIDE A ONE-LINE DIAGRAM SHOWING LOCATIONS OF ALL | | | PANELBOARDS, ALONG WITH CONDUCTOR SIZES. | | | 2. SHOW GROUNDING AND BONDING FOR GENERATORS, AND | | | TRANSFORMERS | | | 3. ALL 15 AND 20 AMP RECEPTACLES SHALL BE GFCI | | | PROTECTED PER 210.8(B)(3), 406.9(B)(1) 590.4(D)(1,2) | | | 4. ALL CORDS AND CABLES SHALL PROTECTED PER 590.4(H | | | 5. PROVIDE CUT SHEETS FOR ALL EXIT AND EMERGENCY | | | LIGHTS. | | | 6. ALL WORK IS SUBJECT TO ELECTRICAL INSPECTOR REVIEW. | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | BN1165, BU1753, PX163 | | | 561-805-6713 | | | |
|