| 2017-03-15 19:03:09 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE WINDOW AND DOOR PRESSURES SPECIFIED ON THE PLANS | | | ARE INCORRECT FOR EXPOSURE C AND A WIND SPEED OF 170 | | | MPH VULT. SUBMIT CALCULATIONS FROM THE ENGINEER SHOWING | | | HOW THE SPECIFIED WINDOW AND DOOR PRESSURES WERE | | | DETERMINED. FBC 107.2.1.3 | | | | | | 2) FBC-R310.1 REQUIRES EACH SLEEPING ROOM TO HAVE AN | | | EMERGENCY ESCAPE AND RESCUE OPENING. SPECIFY THE | | | WINDOWS THAT ARE LOCATED IN THE SLEEPING ROOMS, | | | IDENTIFY THE EXISTING WINDOWS TYPE AND INDICATE HOW YOU | | | WILL COMPLY. ALSO SEE FBC EXISTING BUILDING SECTION | | | 704.1 | | | | | | 3) SUBMIT A COPY OF THE SIGNED CONTRACT TO VERY THE | | | VALUE OF THE WORK. FBC 109.3 |
|