| 2017-03-14 12:17:18 | 1) INDICATE THE REQUIRED FIRE RATING OF THE STAIRWAY ON | | | THE DRAWINGS.FROM THE ORIGINAL DRAWINGS THIS IS A 2 | | | HOUR RATED STAIRWAY. | | | 2) INDICATE THE FIRE RATING OF THE ENCLOSURE FOR THE | | | PIPING ON THE DRAWINGS. THE DRAWINGS NOTE 2 LAYERS OF | | | 5/8 INCH TYPE X DRYWALL ON METAL STUD FRAMING WHICH | | | WOULD PROVIDE AN 80 MINUTE FIRE RATING WHICH IS LESS | | | THAN THE 2 HOUR RATING OF THE ENCLOSURE.THIS PIPING | | | ENCLOSURE SHALL BE THE SAME RATING AS THE ENCLOSURE IN | | | WHICH IT IS LOCATED.FBC 713..4, 713.5. | | | 3) INDICATE THE GAUGE OF THE METAL STUDS BEING USED. | | | | | | TIM LARGE | | | 561-805-6692 | | | [email protected] | | | |
|