Plan Review Notes
Plan Review Notes For Permit 17030455
Permit Number 17030455
Review Stop M
Sequence Number 1
Notes
Date Text
2017-03-22 11:31:191ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17030455
 3/22/17
  
 1) THE NEW CONDENSER UNIT MUST MATCH WITH THE EXISTING
 AIR HANDLER AND THE MATCH MUST BE VERIFIED BY
 SUBMITTING AN AHRI CERTIFICATE, OR MANUFACTURER'S
 LETTER- SEE SECTION C101.4.7 FBC-14 ENERGY
 CONSERVATION.
  
 2) SITE SPECIFIC WIND LOAD ENGINEERING IS REQUIRED FOR
 TIE-DOWN OF THE NEW ROOFTOP CONDENSER PER SECTION
 301.15 FBC-14 MECHANICAL AND SECTION 1609 FBC-14
 BUILDING. THE SUBMITTED PRODUCT APPROVAL FOR THE BMP
 CLIP IS INCOMPLETE- PLEASE PROVIDE THE COVER SHEETS,
 AND MARK ALL APPLICABLE NOTES, DETAILS, DESIGN
 PRESSURES, AND CLIP SIZES ON THE INSTALLATION
 INSTRUCTIONS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved