Plan Review Notes
Plan Review Notes For Permit 17030449
Permit Number 17030449
Review Stop M
Sequence Number 3
Notes
Date Text
2017-05-30 11:52:29MECHANICAL PROVISOS
 5/30/17
  
 1) CLOTHES DRYER EXHAUST DUCTS SHALL NOT EXTEND INTO OR
 THROUGH DUCTS OR PLENUMS- SECTION 504.4 FBC-14
 MECHANICAL.
  
 2) GAS WATER HEATERS AND VENTS:
 503.3.5 AIR DUCTS AND FURNACE PLENUMS.
 VENTING SYSTEMS SHALL NOT EXTEND INTO OR PASS THROUGH
 ANY FABRICATED AIR DUCT OR FURNACE PLENUM.
  
 503.3.6 ABOVE-CEILING AIR-HANDLING SPACES.
 WHERE A VENTING SYSTEM PASSES THROUGH AN ABOVE-CEILING
 AIR-HANDLING SPACE OR OTHER NONDUCTED PORTION OF AN
 AIR-HANDLING SYSTEM, THE VENTING SYSTEM SHALL CONFORM
 TO ONE OF THE FOLLOWING REQUIREMENTS:
  
 1. THE VENTING SYSTEM SHALL BE A LISTED SPECIAL GAS
 VENT; OTHER VENTING SYSTEM SERVING A CATEGORY III OR
 CATEGORY IV APPLIANCE; OR OTHER POSITIVE PRESSURE VENT,
 WITH JOINTS SEALED IN ACCORDANCE WITH THE APPLIANCE OR
 VENT MANUFACTURER?S INSTRUCTIONS.
  
 2. THE VENTING SYSTEM SHALL BE INSTALLED SUCH THAT
 FITTINGS AND JOINTS BETWEEN SECTIONS ARE NOT INSTALLED
 IN THE ABOVE-CEILING SPACE.
  
 3. THE VENTING SYSTEM SHALL BE INSTALLED IN A CONDUIT
 OR ENCLOSURE WITH SEALED JOINTS SEPARATING THE INTERIOR
 OF THE CONDUIT OR ENCLOSURE FROM THE CEILING SPACE.
  
 3) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE GAS FIREPLACE AND VENTING IN THE
 CLUBROOM SHALL BE ONSITE AT TIME OF INSPECTION.
  