 GAS COMMENTS:
  
 1. PLEASE PROVIDE COMBUSTION AIR CALCULATIONS FOR FIRE
 PLACE. PER FBC FG 304
  
 2. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE AND
 TERMINATION OF THE GAS VENTS PER FBC-2014 FUEL GAS CODE
 SEC. 502 THRU 505.
  
 3. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS FOR ALL
 GAS EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA
 54, NFPA 58, AND FBC-2014 FUEL GAS SEC. 402.2
  
 4. SUBMIT MANUFACTURE INSTILLATION GUIDE FOR THE FIRE
 PLACE VENT. PER WPB AMEND TO FBC 107.2.1
  
 5. SHT. P-4.05 THE TOTAL BTU LOAD IS LISTED AS
 4,650,000 BTUS BUT WHEN I COUNTED UP THE WH I CAME UP
 WITH 33 @ 150,00 = 4,950,000 BTUS PLEASE CLARIFY. WPB
 AMEND TO FBC 107.2.1
  
 6. SHT. P-4.06 THE TOTAL BTU LOAD IS LISTED AS
 4,850,000 BTUS BUT WHEN I COUNTED UP THE WH I CAME UP
 WITH 35 @ 150,00 = 5,250,000 BTUS PLEASE CLARIFY. WPB
 AMEND TO FBC 107.2.1
  
  
 FYI A COMPLETE AND THOROUGH REVIEW CANNOT BE DONE AT
 THIS TIME. UPON RESUBMITTAL THERE MAYBE ADDITIONAL
 COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  