2017-05-12 07:48:40BUILDING PLAN REVIEW
 SILVER PALM PLACE
 BLDG # 1/ 66 UNITS/ 4 STORY/ R2/ 2010 TYPE I-B
 W. P. B. REVISION: 17030448
 W. P. B. PERMIT: 15050261
 ADD: 838 ADAMS ST.
 CONT: LANDMARK CONSTRUCTION
 CONTACT: CHARLES ROBERSON
 TEL: 305-665-1146
 E-MAIL: ??????
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: FRI. MAY 12/2017
 SILVER PALM PLACE
 BLDG # 1/ 66 UNITS/ 4 STORY/ R2
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2A) 2ND REQUEST. SHEET A-3.00 NOTES 6 & 10 INDICATE THE
 USE OF PRE-FABRICATED DECORATIVE FOAM OUTLOOKERS AT
 ELEVATION 46FOOT ? 8INCHES. IT HAS RECENTLY BROUGHT TO
 MY ATTENTION THAT FOR FOAM (EFIS) THE CODE SECTION
 1406.2 EXCEPTION: PLASTIC COMPLYING WITH CHAPTER 26. IN
 CHAPTER 26 EFIS. THE EFIS TRIM WILL NEED TO SHOW
 COMPLIANCE WITH 2603.5. EXTERIOR WALLS OF BUILDINGS OF
 TYPE I, II, III OR IV CONSTRUCTION OF ANY HEIGHT SHALL
 COMPLY WITH SECTIONS 2603.5.1 THROUGH 2603.5.7.
 SATISFYING THIS COMMENT ELIMINATES COMMENTS 2B-2E.
  
 COMMENTS FROM 1ST REVIEW. PLEASE REVIEW IN THE 2010
 FBC-B SECTION 1406.2.1 (2) 2. COMBUSTIBLE EXTERIOR WALL
 COVERINGS SHALL BE LIMITED TO 40 FEET (12 192 MM) IN
 HEIGHT ABOVE GRADE PLANE. IN THE 2009 IBC-B COMMENTARY
 IT STATES: ALL EXTERIOR TRIM AND VENEERS ON BUILDINGS
 OF TYPE I, II III AND IV CONSTRUCTION THAT ARE MORE
 THAN 40 FEET ABOVE THE GRADE ARE REQUIRED TO BE
 NON-COMBUSTIBLE.
  
  
 2B) PLEASE IDENTIFY WHERE THE USE OF THE SMOOTH FOAM
 BRACKETS ARE TO BE LOCATED ON THE BUILDING SEE NOTE
 NUMBER 10. THE 2010 FBC-B SECTION 1406.2.1 (2) 2.
 COMBUSTIBLE EXTERIOR WALL COVERINGS SHALL BE LIMITED TO
 40 FEET (12 192 MM) IN HEIGHT ABOVE GRADE PLANE.
  
 2C) SHEET A-3.00 NOTE 17 STATES PRE-FABRICATED
 DECORATIVE BRACKETS BUT THE PLANS DO NOT SPECIFY THE
 TYPE OF MATERIALS. ELEVATION A DOES SHOW THE USE OF
 DECORATIVE BRACKET TYPE 17 ABOVE 40 FEET ABOVE GRADE.
 2010 FBC-B SECTION 1406.2.1 (2) 2. COMBUSTIBLE EXTERIOR
 WALL COVERINGS SHALL BE LIMITED TO 40 FEET (12 192 MM)
 IN HEIGHT ABOVE GRADE PLANE.
  
  
 2D) SHEET A-3.04 DETAIL 10 FOAM BRACKET AT ROOF LINE
 THE DIMENSIONS INDICATED AND THE SCALE 1 INCH = 1 FOOT
 DOES NOT MATCH UP? PLEASE PROVIDE ADDITIONAL
 INFORMATION. 107.2.1.3.
  
 2E) SHEET A-4.2 DETAILS 2 & 3 BOTH SHOW THE USE OF FOAM
 BRACKETS ABOVE THE 40 FOOT FROM GRADE LEVEL. 2010 FBC-B
 SECTION 1406.2.1 (2) 2. COMBUSTIBLE EXTERIOR WALL
 COVERINGS SHALL BE LIMITED TO 40 FEET (12 192 MM) IN
 HEIGHT ABOVE GRADE PLANE.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER