Plan Review Notes
Plan Review Notes For Permit 17030448
Permit Number 17030448
Review Stop B
Sequence Number 1
Notes
Date Text
2017-03-18 11:49:11 
 BUILDING PLAN REVIEW
 SILVER PALM PLACE
 BLDG # 1/ 66 UNITS/ 4 STORY/ R2/ 2010 TYPE I-B
 W. P. B. REVISION: 17030448
 W. P. B. PERMIT: 15050261
 ADD: 838 ADAMS ST.
 CONT: LANDMARK CONSTRUCTION
 CONTACT: CHARLES ROBERSON
 TEL: 305-665-1146
 E-MAIL: ??????
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: SAT. MARCH 18/2017
 SILVER PALM PLACE
 BLDG # 1/ 66 UNITS/ 4 STORY/ R2
  
 1) PLEASE PROVIDE YOUR E-MAIL ADDRESS; WE USE YOUR
 E-MAIL ADDRESS FOR CORRESPONDENCE IN THE FORM OF A
 WRITTEN RECORD. 107.2.1.4 THE BUILDING OFFICIAL MAY
 ESTABLISH THROUGH DEPARTMENTAL POLICY, STANDARDS FOR
 RECORD RETENTION PROGRAM.
  
 2A) SHEET A-3.00 NOTES 6 & 10 INDICATE THE USE OF
 PRE-FABRICATED DECORATIVE FOAM OUTLOOKERS AT ELEVATION
 46?-8?. PLEASE REVIEW IN THE 2010 FBC-B SECTION
 1406.2.1 (2) 2. COMBUSTIBLE EXTERIOR WALL COVERINGS
 SHALL BE LIMITED TO 40 FEET (12 192 MM) IN HEIGHT ABOVE
 GRADE PLANE. IN THE 2009 IBC-B COMMENTARY IT STATES:
 ALL EXTERIOR TRIM AND VENEERS ON BUILDINGS OF TYPE I,
 II III AND IV CONSTRUCTION THAT ARE MORE THAN 40 FEET
 ABOVE THE GRADE ARE REQUIRED TO BE NON-COMBUSTIBLE.
  
 2B) PLEASE IDENTIFY WHERE THE USE OF THE SMOOTH FOAM
 BRACKETS ARE TO BE LOCATED ON THE BUILDING SEE NOTE
 NUMBER 10. THE 2010 FBC-B SECTION 1406.2.1 (2) 2.
 COMBUSTIBLE EXTERIOR WALL COVERINGS SHALL BE LIMITED TO
 40 FEET (12 192 MM) IN HEIGHT ABOVE GRADE PLANE.
  
 2C) SHEET A-3.00 NOTE 17 STATES PRE-FABRICATED
 DECORATIVE BRACKETS BUT THE PLANS DO NOT SPECIFY THE
 TYPE OF MATERIALS. ELEVATION A DOES SHOW THE USE OF
 DECORATIVE BRACKET TYPE 17 ABOVE 40 FEET ABOVE GRADE.
 2010 FBC-B SECTION 1406.2.1 (2) 2. COMBUSTIBLE EXTERIOR
 WALL COVERINGS SHALL BE LIMITED TO 40 FEET (12 192 MM)
 IN HEIGHT ABOVE GRADE PLANE.
  
  
 2D) SHEET A-3.04 DETAIL 10 FOAM BRACKET AT ROOF LINE
 THE DIMENSIONS INDICATED AND THE SCALE 1 INCH = 1 FOOT
 DOES NOT MATCH UP? PLEASE PROVIDE ADDITIONAL
 INFORMATION. 107.2.1.3.
  
 2E) SHEET A-4.2 DETAILS 2 & 3 BOTH SHOW THE USE OF FOAM
 BRACKETS ABOVE THE 40 FOOT FROM GRADE LEVEL. 2010 FBC-B
 SECTION 1406.2.1 (2) 2. COMBUSTIBLE EXTERIOR WALL
 COVERINGS SHALL BE LIMITED TO 40 FEET (12 192 MM) IN
 HEIGHT ABOVE GRADE PLANE.
  
 3) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  