| 2017-03-24 09:19:30 | 1ST REVIEW FBC-2014 MECHANICAL | | | PERMIT #17030438 | | | 3/24/17 | | | | | | 1) SHEET M0.1: PROVIDE THE DEPTH OF EMBEDMENT FOR THE | | | CU WEDGE ANCHOR BOLTS. | | | | | | 2) M0.1: THE DRYBULB AND WETBULB TEMPERATURES IN THE | | | HVAC DESIGN CONDITIONS TABLE ARE INCORRECT FOR WEST | | | PALM BEACH PER ACCA MANUAL N. FROM WHICH STANDARD WERE | | | THESE TEMPERATURES DERIVED? | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|