| Plan Review Notes For Permit 17030438 |
| Permit Number |
17030438 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-29 07:14:38 | CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70 2011 EDITION | | | | | | | | | NEED TO SHOW LOCATION OF THE METER, IS METER CT OR | | | VOLTAGE. | | | FAULT CURRENT CALCULATION AND SIGNAGE NEC 110.24(A)(B) | | | NO GROUNDING SHOWN FOR THE SERVICE. | | | ENERGY CALCULATION FBC EC C405.5.2 | | | | | | | | | JAKE LEAHY | | | ELECTRICAL INSPECTOR II | | | 561-805-6713 | | | [email protected] | | | |
|