| 2017-03-13 16:03:35 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | |
| | 1) THE SUBMITTED PLANS DO NOT INDICATE ANY EXISTING |
| | FIRE SPRINKLER AND/OR FIRE ALARM DEVICES/EQUIPMENT. |
| | |
| | PLEASE INDICATE ANY EXISTING FIRE SPRINKLER AND/OR FIRE |
| | ALARM DEVICES/EQUIPMENT. |
| | |
| | |
| | |
| | |
| | 2) ANY REMOVAL AND/OR CONSTRUCTION OF WALLS AND /OR |
| | CEILINGS REQUIRE AN EVALUATION OF THE FIRE ALARM AND |
| | SPRINKLER SYSTEM FOR CODE COVERAGE AND COMPLIANCE BY |
| | CERTIFIED LIFE SAFETY CONTRACTORS. |
| | |
| | THE LIFE SAFETY SYSTEMS, FIRE ALARM AND/OR FIRE |
| | SPRINKLER SHALL REMAIN ACTIVE THROUGHOUT THE |
| | CONSTRUCTION PERIOD. |
| | |
| | ANY AND ALL WORK ON THE FIRE ALARM AND FIRE SPRINKLER |
| | SYSTEMS SHALL BE DONE UNDER SEPARATE SHOP DRAWINGS AND |
| | BY CERTIFIED LIFE SAFETY CONTRACTORS. |
| | |
| | ANY TIME THAT WORK ON THE LIFE SAFETY SYSTEMS, |
| | SPRINKLER AND/OR FIRE ALARM, EXCEEDS 4 HOURS, A FIRE |
| | WATCH SHALL BE IMPLEMENTED AND MAINTAINED UNTIL FULL |
| | AND COMPLETE PROTECTION IS RETURNED. |
| | |
| | |
| | |
| | |
| | |
| | 3) THERE WAS NO LIFE SAFTY PLAN SUBMITTED. |
| | |
| | PLEASE PROVIDE A COMPLETE LIFE SAFETY PLANS THAT |
| | ILLUSTRATES OCCUPANT LOADS, TRAVEL DISTANCES, COMMON |
| | PATHS OF TRAVEL, DEAD-END CORRIDORS, EXIT SIGNS, |
| | EMERGENCY LIGHTING, EXITS LEADING TO A PUBLIC WAY, FIRE |
| | EXTINGUISHER LOCATIONS, AND ALL FIRE SAFETY FEATURES |
| | AND EQUIPMENT. |
| | |
| | |
| | |
| | |
| | 4) THERE WAS NO INDICATION OR COMPLIANCE WITH THE |
| | FLORIDA FIRE PREVENTION CODE. |
| | |
| | PLEASE PROVIDE A NOTE CONFIRMING COMPLIANCE WITH THE |
| | REQUIREMENTS OF THE 5TH EDITION OF FLORIDA FIRE |
| | PREVENTION CODE INCLUDING THE 2012 EDITION OF NFPA 1 |
| | AND NFPA 101 AND ALL OTHER APPLICABLE CODES OR |
| | STANDARDS. |
| | |
| | |
| | |
| | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | |
| | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |