 PLUMBING COMMENTS:
  
 1. ALL THE LAVS NEED TO BE VENTED WASHING MACHINE AND
 LAUNDRY SINK NEEDS A VENT. PER FBC RES P3101.2.1
  
 2. THE KITCHEN IS NOT SHOWN ON RISER DIAGRAM PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 3. THE BRANCH DRAIN CONNECTING THE LAVS AND SHOWER AND
 TUB IN MASTER BATHROOM IS UNDER SIZED NO MORE THAN TWO
 FIXTURES CAN BE CONNECT TO 11/2" . PER FBC RES TABLE
 P3005.4.2 NOTE A
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  