| 2017-03-14 09:48:57 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | |
| | 1) |
| | SHEET LS 1 - THERE IS NO INDICATION OF THE |
| | CLASSIFICATION OF OCCUPANY; MIXED OR SEPARATED; |
| | |
| | PER NFPA 101, 5TH ED |
| | |
| | 6.1.14.1.1 MULTIPLE OCCUPANCIES SHALL COMPLY WITH THE |
| | REQUIREMENTS OF 6.1.14.1 AND ONE OF THE FOLLOWING: |
| | (1) MIXED OCCUPANCIES ? 6.1.14.3 |
| | (2) SEPARATED OCCUPANCIES ? 6.1.14.4 |
| | |
| | 6.1.14.2.1 MULTIPLE OCCUPANCY. A BUILDING OR STRUCTURE |
| | IN WHICH TWO OR MORE CLASSES OF OCCUPANCY EXIST. |
| | 6.1.14.2.2 MIXED OCCUPANCY. A MULTIPLE OCCUPANCY WHERE |
| | THE OCCUPANCIES ARE INTERMINGLED. |
| | 6.1.14.2.3 SEPARATED OCCUPANCY. A MULTIPLE OCCUPANCY |
| | WHERE THE OCCUPANCIES ARE SEPARATED BY FIRE |
| | RESISTANCE?RATED ASSEMBLIES. |
| | 6.1.14.3 MIXED OCCUPANCIES. |
| | 6.1.14.3.1 EACH PORTION OF THE BUILDING SHALL BE |
| | CLASSIFIED AS TO ITS USE IN ACCORDANCE WITH SECTION 6.1 |
| | 6.1.14.3.2* THE BUILDING SHALL COMPLY WITH THE MOST |
| | RESTRICTIVE REQUIREMENTS OF THE OCCUPANCIES INVOLVED, |
| | UNLESS SEPARATE SAFEGUARDS ARE APPROVED. |
| | |
| | PLEASE INDICATE THE INTENT OF THE OCCUANCY |
| | CLASSIFICATION AND ENSURE THE MOST RESTRICTIVE |
| | REQUIRMENTS ARE MET. |
| | |
| | |
| | 2) |
| | SHEET LS 1 - THERE ARE NO INDICATIONS OF THE |
| | DESCRIPTION OF THE HAZARD CLASSIFICATION |
| | |
| | 6.2.1.2 HAZARD OF CONTENTS SHALL BE CLASSIFIED BY THE |
| | REGISTERED DESIGN PROFESSIONAL (RDP) OR OWNER AND |
| | SUBMITTED TO THE AUTHORITY HAVING JURISDICTION FOR |
| | REVIEW AND APPROVAL ON THE BASIS OF THE CHARACTER OF |
| | THE CONTENTS AND THE PROCESSES OR OPERATIONS CONDUCTED |
| | IN THE BUILDING OR STRUCTURE. |
| | |
| | PLEASE PROVIDE A DETAILED THE PROPOSED CONTECT OF THE |
| | STORAGE, INCLUDING BUT NOT LIMITED TO, PRODUCT, |
| | PALLETS, PACKAGING, RACKS, RACK HEIGHTS, ETC. |
| | |
| | |
| | |
| | 3) |
| | SHEET LS 1 - THERE AR NO INDICATIONS OF THE DOORS LOCKS |
| | ON THE EXIT DOORS EITHER AT THE DOUBLE FRONT DOOR AR |
| | BOTH WAREHOUSE DOORS. ALL HARDWARE SHALL COMPLY WITH |
| | NFPA 101, CHAPTER 7, MEANS OF EGRESS AND/OR THE MOST |
| | RESTRICTIVE OCCUPANY AS DETERMINED BY # 1 ABOVE. |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM THE EGRESS SIDE WHENEVER THE BUILDING IS |
| | OCCUPIED. |
| | 7.2.1.5.2* THE REQUIREMENT OF 7.2.1.5.1 SHALL NOT APPLY |
| | TO DOOR LEAVES OF LISTED FIRE DOOR ASSEMBLIES AFTER |
| | EXPOSURE TO ELEVATED TEMPERATURE IN ACCORDANCE WITH THE |
| | LISTING, BASED ON LABORATORY FIRE TEST PROCEDURES. |
| | 7.2.1.5.3 LOCKS, IF PROVIDED, SHALL NOT REQUIRE THE USE |
| | OF A KEY, A TOOL, OR SPECIAL KNOWLEDGE OR EFFORT FOR |
| | OPERATION FROM THE EGRESS SIDE. |
| | |
| | 7.2.1.5.5 KEY-OPERATED LOCKS. |
| | 7.2.1.5.5.1 EXTERIOR DOOR ASSEMBLIES SHALL BE PERMITTED |
| | TO HAVE KEYOPERATED LOCKS FROM THE EGRESS SIDE, |
| | PROVIDED THAT ALL OF THE FOLLOWING CRITERIA ARE MET: |
| | (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11 |
| | THROUGH 43 FOR THE SPECIFIC OCCUPANCY. |
| | (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS |
| | THAN 1 IN. (25 MM) HIGH ON A CONTRASTING BACKGROUND |
| | THAT READS AS FOLLOWS IS LOCATED ON OR ADJACENT TO THE |
| | DOOR LEAF: THIS DOOR TO REMAIN UNLOCKED WHEN THE |
| | BUILDING IS |
| | OCCUPIED. |
| | (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY |
| | DISTINGUISHABLE AS LOCKED. |
| | (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT |
| | INSIDE THE BUILDING WHEN IT IS LOCKED. |
| | |
| | 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR |
| | LEAF SHALL BE PROVIDED WITH A RELEASING DEVICE THAT HAS |
| | AN OBVIOUS METHOD OF OPERATION AND THAT IS READILY |
| | OPERATED UNDER ALL LIGHTING CONDITIONS. |
| | 7.2.1.5.10.1 THE RELEASING MECHANISM FOR ANY LATCH |
| | SHALL BE LOCATED AS FOLLOWS: |
| | (1) NOT LESS THAN 34 IN. (865 MM) ABOVE THE FINISHED |
| | FLOOR FOR OTHER THAN EXISTING INSTALLATIONS |
| | (2) NOT MORE THAN 48 IN. (1220 MM) ABOVE THE FINISHED |
| | FLOOR 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN |
| | THE DOOR LEAF WITH NOT MORE THAN ONE RELEASING |
| | OPERATION, UNLESS OTHERWISE SPECIFIED IN 7.2.1.5.10.3, |
| | 7.2.1.5.10.4, OR 7.2.1.5.10.6. |
| | |
| | PLEASE PROVIDE DETAILS MEETING THE REQUIREMENTS. |
| | |
| | |
| | |
| | 4) |
| | WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET REVISION |
| | CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE ABOVE. |
| | |
| | |
| | |
| | 5) |
| | ADDITIONAL COMMENTS MAY BE PROVIDED ON THE RE-SUBMITTAL |
| | OF THE ABOVE. |
| | |
| | |
| | |
| | PETER LEDUC |