| Plan Review Notes For Permit 17030344 |
| Permit Number |
17030344 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-27 16:23:07 | JAKE LEAHY | | | ELECTRICAL INSPECTOR II | | | 561-805-6713 | | | [email protected] | | | | | | FBCE C405.5.2.INTERIOR LIGHTING POWER. THE TOTAL | | | INTERIOR LIGHTING POWER ALLOWANCE (WATTS) IS DETERMINED | | | ACCORDING TO TABLE C405.5.2(1) USING THE BUILDING AREA | | | METHOD, OR TABLE C405.5.2(2) USING THE SPACE-BY-SPACE | | | METHOD, FOR ALL AREAS OF THE BUILDING COVERED IN THIS | | | PERMIT. | | | | | | 2011 NEC 210.5 (C)(3) CIRCXUIT NUMBERS ON PLANS | | | | | | 2011 NEC 215.5 RISER DIAGRAM | | | | | | 2011 NEC 422.52 DRINKING FOUNTAINS TO BE GFCI | | | PROTECTED. | | | | | | PLAN SHOWS WAREHOUSE PLEASE INCLUDE FLOOR PLANS |
|