2017-03-16 14:30:13BUILDING PLAN REVIEW
 W. P. B. PERMIT: 17030344
 ADD: 1500 FLORIDA MANGO ROAD SUITES 9A & 10
 CONT: MALASKY HOMES
 TEL: 561-471-8600
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURS. MARCH 16/ 2017
 ACTION: DENIED
  
 1) THE LIFE SAFETY SHEET INDICATES THIS IS A S2
 OCCUPANCY AND THE OFFICE BEING AN ACCESSORY OCCUPANCY.
 WITH THE S2 OCCUPANCY DECLARED AS 5760 SQ. FT. AND THE
 BUSINESS/ OFFICE 1,419 SQ. FT. THE BUSINESS OCCUPANCY
 IS OVER 10 % OF THE FLOOR AREA, CLOSER TO 25% MAKING
 THIS A MIXED USE OCCUPANCY. SEE 2014 FBC-B 508.2.1 AREA
 LIMITATIONS. AGGREGATE ACCESSORY OCCUPANCIES SHALL NOT
 OCCUPY MORE THAN 10 PERCENT OF THE BUILDING AREA.
  
 2) THE LIFE SAFETY PLAN INDICATES THE STORAGE OCCUPANCY
 TO BE AN S2. PLEASE LIST THE TYPES OF ARTICLES TO BE
 STORED IN THIS FACILITY CLASSIFYING IT AN S2 TYPE OF
 OCCUPANCY. FBC-B 311.3 LOW-HAZARD STORAGE- GROUP S-2.
  
 3) THE LIFE SAFETY SHEET SHOWS WHAT APPEARS TO BE A NEW
 OPENING BETWEEN THE 2 TENANT SPACES IDENTIFIED 9B AND
 UNIT 10. THIS IS AN OCCUPANCY SEPARATION WALL WHICH
 WOULD REQUIRE FIRE RATING FOUND IN FBC-B TABLE 508.4
 FOR FIRE SPRINKLERED BUILDINGS A 1 HOUR, SEE OPENING
 PROTECTIVES TABLE 716.5.
  
 4) SHEET A-1 DETAIL # 1 INDICATES THE ENCLOSING OF A 12
 FOOT HIGH 10 FOOT WIDE OVERHEAD DOOR OPENING. THIS SAME
 DETAIL HAS SECTION 1A & 2. THIS DETAIL IS NOT CLEAR AS
 TO THE METAL STUD HEADER. THE PLANS ARE SILENT TO THE
 SIZE OF THE STUDS, GAUGE OF METAL, YIELD STRENGTH, HOW
 THE BOXED HEADER WILL ATTACH TO THE (COLUMNS) MAIN WIND
 FORCE RESISTING SYSTEM? THE PLANS ALSO DO NOT PROVIDE
 THE SIZE OF THE EXTERIOR BEARING WALL STEEL STUD
 INFILL. 2014 FBC-B 2211.4 WALL STUD DESIGN.
  
 5) SHEET A-1 DETAIL # 1 PLEASE PROVIDE THE WIND DESIGN
 CRITERIA PER 2014 FBC-B 1603.1.4. THE FOLLOWING
 INFORMATION RELATED TO WIND LOADS SHALL BE SHOWN,
 REGARDLESS OF WHETHER WIND LOADS GOVERN THE DESIGN OF
 THE LATERAL FORCE-RESISTING SYSTEM OF THE STRUCTURE:
 5.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND GUST),
 MILES PER HOUR (KM/HR) AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
 5.2. RISK CATEGORY.
 5.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
 5.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
 5.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF (KN/
 M2).
  
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 6) THE MIAMI-DADE NOA 15-0618.01 3000 RESISTOR
 STOREFRONT WINDOW WALL SYSTEM WAS SUBMITTED. THIS IS
 FOR THE SIDELIGHTS ONLY!!! FOR ALL PRODUCTS WITH
 GLAZING, PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT,
 TYPE OF GLAZING, MULLION INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE.
 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 7) 2014 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,MULLIONS
  
 8) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 9) SHEET MEP DETAILS 1, 2 & 3 ALL SHOW INSULATION LAID
 IN ON THE DROP CEILING, WHAT IS THIS INSULATION TO BE
 USED FOR? 2014 FBC-ENERGY C402.2.1 INSULATION INSTALLED
 ON A SUSPENDED CEILING WITH REMOVALABLE CEILING TILES
 SHALL NOT BE CONSIDERED PART OF THE MINIMUM THERMAL
 RESISTANCE OF THE ROOF INSULATION.
  
 10) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  