2017-03-13 11:05:55INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 PLEASE SHOW ON MEP SHEET THE EMERGENCY FIXTURES AS
 SHOWN ON LIFE SAFETY SHEET. ELECTRICAL SCOPE TO
 COORELATE. FBC 107.3.5
  
 CLARIFY IF INTERIOR LIGHTING CONTROLS ARE ON OCCUPANCY
 SENSORS TO AUTOMATICALLY CONTROL THE LIGHTING. FBC EC
 405
  
 PROVIDE THE PANEL SCHEDULE ASSOCIATED WITH THIS OFFICE
 SUITE. FBC 107.3.5
  
 ANY LOW VOLTAGE SYSTEM ALTERATION WILL REQUIRE SEPERATE
 PERMIT. GENERAL NOTE WILL SUFFICE.
  
 VAL PEREZ
 ELECTRICAL PLANS EXAMINER
 *6717
  
  