| 2017-03-13 13:58:09 | BUILDING PLAN REVIEW |
| | W. P. B. PERMIT: 17030329 |
| | ADD: 1401 FORUM WAY SUITE # 501 |
| | CONT: CLAY KOHLMEYER |
| | TEL: 561-694-1214 |
| | E-MAIL: [email protected] |
| | |
| | 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| | ADMINISTRATION |
| | |
| | 2014 EXISTING BUILDING CODE LEVEL II 701.3 COMPLIANCE. |
| | ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| | SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| | FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. MARCH 13, 2017 |
| | ACTION: DENIED |
| | |
| | 1) DISCREPANCY IN PLANS. 107.2.1.3 ADDITIONAL |
| | INFORMATION REQUIRED. THE COVERSHEET CS-1 INDICATES THE |
| | CONSTRUCTION TYPE TO BE IIB- UNPROTECTED SPRINKLERED |
| | WHEREAS THE LIFE SAFETY SHEET LS-1 INDICATES THE |
| | BUILDING TYPE OF CONSTRUCTION TO BE A IB. IB TYPE OF |
| | CONSTRUCTION IS PROTECTED SEE FBC-B TABLE 601 AND IS |
| | FIRE SPRINKLERED. |
| | |
| | 2) THE PLAN A-1.0 INDICATES A PARTITION TYPE LEGEND. |
| | THE PARTITION TYPE IDENTIFIED ?C? IS TO BE USED WITH A |
| | X-RAY ROOM. NEITHER THE LIFE SAFETY SHEET NOR A-1.0 |
| | SHOW THE USE OF AN X-RAY ROOM. IS THERE ANY ROOMS THAT |
| | WILL REQUIRE SHIELDING AS FOUND IN SECTION 465.1 FOR |
| | X-RAY ROOMS OR IS THIS A GENERIC NOTE THAT HAS NOTHING |
| | TO DO WITH THIS TENANT SPACE. IF X-RAY EQUIPMENT IS TO |
| | BE INSTALLED IN THIS TENANT SPACE PLEASE INDICATE THE |
| | TYPE OF USAGE, THE MACHINES CAPACITY OF STRENGTH IN |
| | KEV. FBC-B 465.1.3. A THOROUGH REVIEW CANNOT BE MADE AT |
| | THIS TIME, AS A RESULT OF THE ADDITIONAL INFORMATION |
| | REQUESTED ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT |
| | PART OF THIS REVIEW. |
| | |
| | 3) THE PLAN A-1.0 INDICATES A DOOR SCHEDULE WITH THE |
| | DESIGNATION OF R FOR DOORS TO BE RELOCATED. THESE DOORS |
| | ARE IN A NEW WALL LOCATION. 2014 EXISTING BUILDING CODE |
| | LEVEL II 701.3 COMPLIANCE. ALL NEW CONSTRUCTION |
| | ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY |
| | WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE, |
| | BUILDING. PLEASE PROVIDE THE SIZE OF THE DOOR IN THE |
| | DOOR SCHEDULE AND COMPLIANCE WITH 2014 FBC-B 1008.1.1 |
| | SIZE OF DOOR. |
| | |
| | 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| | & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| | NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER BN, PX, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |