| Notes |
| Date |
Text |
| 2017-03-15 13:47:51 | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 NEC | | | COMMENTS: | | | | | | 1. PLEASE SHOW ON ROOFTOP PLAN THE REQUIRED 3FT CLEAR | | | PATHWAYS FOR EMERGENCY RESPONDERS. | | | 2. DELETE REFRENCE TO 2006 IBC CODE FROM PLANS | | | 3. PROVIDE ALL MANUF. SPECS FOR INVERTER, RACKING | | | SYSTEMS AND COMPONENTS WITH INSTALLATION INSTRUCTION, | | | WEATHER PROFFING AND SOLAR PANELS. FBC 107.3.5 | | | 4. FURTHER COMMENTS MAY FOLLOW UPON RESUBMITTAL. FEEL | | | FREE TO CONTACT ME AT THE NUMBER BELOW, SHOULD YOU HAVE | | | ANY QUESTIONS OR CONCERNS. | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | | | | |
|