Plan Review Notes
Plan Review Notes For Permit 17030265
Permit Number 17030265
Review Stop P
Sequence Number 1
Notes
Date Text
2017-03-16 09:38:541ST REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. ELIMINATING THE TOILET MAY BRING THE REQUIRED
 FIXTURE COUNT BELOW THE NUMBER REQUIRED FOR THIS
 OCCUPANCY TYPE AND OCCUPANT LOAD. PER FBC PL TABLE
 403.1 PLEASE PROVIDE OCCUPANT LOAD AND FIXTURE COUNT
 FOR SPACE. PER WPB AMEND TO FBC 107.2.1
  
 2. PLEASE PROVIDE RISER DIAGRAM FOR NEW WASHING
 MACHINE. PER WPB AMEND 107.3.5.1.3(13)
  
 3. SHOW ACCESSIBILITY REQUIREMENTS FOR NEW SHOWER. PER
 FBC ACC 213.3.6 BATHING FACILITIES.
 WHERE BATHTUBS OR SHOWERS ARE PROVIDED, AT LEAST ONE
 BATHTUB COMPLYING WITH 607 OR AT LEAST ONE SHOWER
 COMPLYING WITH 608 SHALL BE PROVIDED.
  
 4. ADA BATH #1 DOES NOT COMPLY WITH FBC ACC
 604.3.1 SIZE.
 CLEARANCE AROUND A WATER CLOSET SHALL BE 60 INCHES
 (1525 MM) MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES (1420 MM) MINIMUM MEASURED
 PERPENDICULAR FROM THE REAR WALL.
  
 DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND
 THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON
 RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS.
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  