| 2017-03-16 12:31:47 | BUILDING PLAN REVIEW |
| | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| | ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | BUILDING PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | |
| | 1ST REVIEW |
| | RESULTS: DENIED |
| | |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | 1. PREVIOUS APPLICATION # 16010004 - CHANGE OF |
| | USE/OCCUPANCY FROM DOCTOR'S OFFICE TO TEMPORARY FIRE |
| | STATION #9 HAS EXPIRED. |
| | 2. IT WAS RECOMMENDED TO HAVE A DESIGN PROFESSIONAL |
| | SUBMIT PLANS. NO PLANS ON FILE, |
| | 3. LIFE SAFETY ISSUES WERE NEVER ADDRESSED: SMOKE |
| | ALARMS, FIRE ALARM, ADDITIONAL EXIT SIGN. |
| | 4. THIS CURRENT APPLICATION IS FOR THE RENOVATION OF |
| | ACCESSIBLE TOILET ROOM #2: INSTALLATION OF A NEW |
| | SHOWER. |
| | 4A. CANNOT VERIFY SHOWER OR ROOM COMPLIES WITH THE |
| | ACCESSIBILITY CODE. INSUFFICIENT INFORMATION ON PLAN: |
| | CLEAR FLOOR SPACE, GRAB BARS, CONTROLS LOCATION, |
| | ROLL-IN ACCESS, ETC. |
| | |
| | SECTION 111 CERTIFICATE OF OCCUPANCY |
| | [A] 111.1 USE AND OCCUPANCY. |
| | NO BUILDING OR STRUCTURE SHALL BE USED OR OCCUPIED, AND |
| | NO CHANGE IN THE EXISTING OCCUPANCY CLASSIFICATION OF A |
| | BUILDING OR STRUCTURE OR PORTION THEREOF SHALL BE MADE, |
| | UNTIL THE BUILDING OFFICIAL HAS ISSUED A CERTIFICATE OF |
| | OCCUPANCY THEREFOR AS PROVIDED HEREIN. ISSUANCE OF A |
| | CERTIFICATE OF OCCUPANCY SHALL NOT BE CONSTRUED AS AN |
| | APPROVAL OF A VIOLATION OF THE PROVISIONS OF THIS CODE |
| | OR OF OTHER ORDINANCES OF THE JURISDICTION. |
| | |
| | SECTION 108 TEMPORARY STRUCTURES AND USES |
| | [A] 108.1 GENERAL. |
| | THE BUILDING OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT |
| | FOR TEMPORARY STRUCTURES AND TEMPORARY USES. SUCH |
| | PERMITS SHALL BE LIMITED AS TO TIME OF SERVICE, BUT |
| | SHALL NOT BE PERMITTED FOR MORE THAN 180 DAYS. THE |
| | BUILDING OFFICIAL IS AUTHORIZED TO GRANT EXTENSIONS FOR |
| | DEMONSTRATED CAUSE. |
| | |
| | 603 TOILET AND BATHING ROOMS |
| | 603.1 GENERAL. |
| | TOILET AND BATHING ROOMS SHALL COMPLY WITH 603. |
| | 603.2 CLEARANCES. |
| | CLEARANCES SHALL COMPLY WITH 603.2. |
| | 603.2.1 TURNING SPACE. |
| | TURNING SPACE COMPLYING WITH 304 SHALL BE PROVIDED |
| | WITHIN THE ROOM. |
| | 603.2.2 OVERLAP. |
| | REQUIRED CLEAR FLOOR SPACES, CLEARANCE AT FIXTURES, AND |
| | TURNING SPACE SHALL BE PERMITTED TO OVERLAP. |
| | 603.2.3 DOOR SWING. |
| | DOORS SHALL NOT SWING INTO THE CLEAR FLOOR SPACE OR |
| | CLEARANCE REQUIRED FOR ANY FIXTURE. DOORS SHALL BE |
| | PERMITTED TO SWING INTO THE REQUIRED TURNING SPACE. |
| | |
| | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| | UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED AND MARK VOID. |
| | |
| | |
| | |
| | |