| Plan Review Notes For Permit 17030233 |
| Permit Number |
17030233 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-20 13:12:35 | PASSED WITH PROVISO: | | | | | | PROVIDE REVISED AVAILABLE FAULT CURRENT CALCULATION FOR | | | THE NEW SERVICE SHOWN AND LABEL SERVICE UPON FINAL | | | INSPECTION WITH AIC. NEC 110.24A | | | | | | SITE LIGHT, YARD LIGHTS TO BE UNDER SEPERATE PERMIT. | | | ANY LOW VOLTAGE AS WELL. FBC 107.3.5 | | | | | | A SECOND MEANS OF GROUNDING REQUIRED TO SUPPLEMENT THE | | | ONE GROUND ROD SHOWN. PROVIDE TWO RODS. | | | | | | V. PEREZ | | | *6717 |
|