| 2017-06-16 09:46:49 | BUILDING PLAN REVIEW |
| | 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH |
| | AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1 |
| | ADMINISTRATION |
| | |
| | CHRISTOPHER S. THROOP, C.B.O. |
| | PLANS EXAMINER, PX3169 |
| | CONSTRUCTION SERVICES DIVISION |
| | TEL: 561-805-6726 |
| | FAX: 561-805-6676 |
| | |
| | 4TH REVIEW |
| | RESULTS: DENIED |
| | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| | |
| | THE FOLLOWING ITEMS HAVE NOT BEEN CORRECTED FROM LAST |
| | REVIEW. |
| | |
| | 1. SEE COMMENT #1 - DIMENSION FROM THE NOSING TO THE |
| | TOP OF THE HANDRAIL IS SPECIFIED AS 30" (SEE PLAN PAGE |
| | S-303). DIMENSION TO BE NOT LESS THAN 34" NOR MORE THAN |
| | 38" PER FBC-R311.7.8.1. |
| | R311.7.8.1 HEIGHT. |
| | HANDRAIL HEIGHT, MEASURED VERTICALLY FROM THE SLOPED |
| | PLANE ADJOINING THE TREAD NOSING, OR FINISH SURFACE OF |
| | RAMP SLOPE, SHALL BE NOT LESS THAN 34 INCHES (864 MM) |
| | AND NOT MORE THAN 38 INCHES (965 MM). |
| | |
| | 2. SEE COMMENT #3 - NOTE #15 ON PLAN SHEET S-102 STATES |
| | DRAFTSTOPPING SHALL NOT EXCEED 100 SF. FBC -R302.12 |
| | STATES AREA NOT TO EXCEED 1000 SF. |
| | R302.12 DRAFTSTOPPING. |
| | IN COMBUSTIBLE CONSTRUCTION WHERE THERE IS USABLE SPACE |
| | BOTH ABOVE AND BELOW THE CONCEALED SPACE OF A |
| | FLOOR/CEILING ASSEMBLY, DRAFTSTOPS SHALL BE INSTALLED |
| | SO THAT THE AREA OF THE CONCEALED SPACE DOES NOT EXCEED |
| | 1,000 SQUARE FEET (92.9 M2). DRAFTSTOPPING SHALL DIVIDE |
| | THE CONCEALED SPACE INTO APPROXIMATELY EQUAL AREAS. |
| | WHERE THE ASSEMBLY IS ENCLOSED BY A FLOOR MEMBRANE |
| | ABOVE AND A CEILING MEMBRANE BELOW, DRAFTSTOPPING SHALL |
| | BE PROVIDED IN FLOOR/CEILING ASSEMBLIES UNDER THE |
| | FOLLOWING CIRCUMSTANCES: |
| | |
| | 3. SEE COMMENT #5 - PRODUCT APPROVALS TO BE REVIEWED |
| | AND APPROVED BY DESIGNER OF RECORD PER FBC-R107.3.4. |
| | SUBMITTED NOA 16-0629.16 FOR FRENCH DOORS IS NOT ON |
| | APPROVED PRODUCT APPROVAL LIST (SEE PLAN SHEET S-000). |
| | FBC 107.3.4.1 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | - THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | 4. SEE COMMENT #6 - MANUFACTURERS INSTALLATION |
| | INSTRUCTIONS SUBMITTED FOR OUTDOOR BBQ. SAFE OPERATING |
| | PRACTICES PROHIBIT OPERATION UNDER OVERHEAD COMBUSTIBLE |
| | CONSTRUCTION. SUMMER KITCHEN CEILING IS T&G. PLEASE |
| | MCLARIFY. |
| | |
| | 5. SEE COMMENT #7 - NOA 16-0629.14 FOR ARCH TOP ENTRY |
| | DOORS (FIXED WINDOW) SUBMITTED FOR REVIEW IS NOT ON |
| | APPROVED PRODUCT APPROVAL LIST (SEE PLAN PAGE S-000). |
| | FBC 107.3.4.1 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| | - THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3 |
| | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| | JURISDICTIONAL APPROVAL. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| | REVIEWED SHEETS DETACHED AND MARK VOID. |
| | |
| | |
| | |
| | |
| | |
| | |