Plan Review Notes
Plan Review Notes For Permit 17030227
Permit Number 17030227
Review Stop B
Sequence Number 4
Notes
Date Text
2017-06-16 09:46:49BUILDING PLAN REVIEW
 2014 FLORIDA BUILDING CODE W/2010 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1
 ADMINISTRATION
  
 CHRISTOPHER S. THROOP, C.B.O.
 PLANS EXAMINER, PX3169
 CONSTRUCTION SERVICES DIVISION
 TEL: 561-805-6726
 FAX: 561-805-6676
  
 4TH REVIEW
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
  
 THE FOLLOWING ITEMS HAVE NOT BEEN CORRECTED FROM LAST
 REVIEW.
  
 1. SEE COMMENT #1 - DIMENSION FROM THE NOSING TO THE
 TOP OF THE HANDRAIL IS SPECIFIED AS 30" (SEE PLAN PAGE
 S-303). DIMENSION TO BE NOT LESS THAN 34" NOR MORE THAN
 38" PER FBC-R311.7.8.1.
 R311.7.8.1 HEIGHT.
 HANDRAIL HEIGHT, MEASURED VERTICALLY FROM THE SLOPED
 PLANE ADJOINING THE TREAD NOSING, OR FINISH SURFACE OF
 RAMP SLOPE, SHALL BE NOT LESS THAN 34 INCHES (864 MM)
 AND NOT MORE THAN 38 INCHES (965 MM).
  
 2. SEE COMMENT #3 - NOTE #15 ON PLAN SHEET S-102 STATES
 DRAFTSTOPPING SHALL NOT EXCEED 100 SF. FBC -R302.12
 STATES AREA NOT TO EXCEED 1000 SF.
 R302.12 DRAFTSTOPPING.
 IN COMBUSTIBLE CONSTRUCTION WHERE THERE IS USABLE SPACE
 BOTH ABOVE AND BELOW THE CONCEALED SPACE OF A
 FLOOR/CEILING ASSEMBLY, DRAFTSTOPS SHALL BE INSTALLED
 SO THAT THE AREA OF THE CONCEALED SPACE DOES NOT EXCEED
 1,000 SQUARE FEET (92.9 M2). DRAFTSTOPPING SHALL DIVIDE
 THE CONCEALED SPACE INTO APPROXIMATELY EQUAL AREAS.
 WHERE THE ASSEMBLY IS ENCLOSED BY A FLOOR MEMBRANE
 ABOVE AND A CEILING MEMBRANE BELOW, DRAFTSTOPPING SHALL
 BE PROVIDED IN FLOOR/CEILING ASSEMBLIES UNDER THE
 FOLLOWING CIRCUMSTANCES:
  
 3. SEE COMMENT #5 - PRODUCT APPROVALS TO BE REVIEWED
 AND APPROVED BY DESIGNER OF RECORD PER FBC-R107.3.4.
 SUBMITTED NOA 16-0629.16 FOR FRENCH DOORS IS NOT ON
 APPROVED PRODUCT APPROVAL LIST (SEE PLAN SHEET S-000).
 FBC 107.3.4.1 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 - THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 4. SEE COMMENT #6 - MANUFACTURERS INSTALLATION
 INSTRUCTIONS SUBMITTED FOR OUTDOOR BBQ. SAFE OPERATING
 PRACTICES PROHIBIT OPERATION UNDER OVERHEAD COMBUSTIBLE
 CONSTRUCTION. SUMMER KITCHEN CEILING IS T&G. PLEASE
 MCLARIFY.
  
 5. SEE COMMENT #7 - NOA 16-0629.14 FOR ARCH TOP ENTRY
 DOORS (FIXED WINDOW) SUBMITTED FOR REVIEW IS NOT ON
 APPROVED PRODUCT APPROVAL LIST (SEE PLAN PAGE S-000).
 FBC 107.3.4.1 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE
 - THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE 9N-3
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY
 REVIEWED SHEETS DETACHED AND MARK VOID.
  
  
  
  
  
  