2017-05-30 13:57:05PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) ON SHEET S-303, THE DIMENSION FROM THE NOSING TO THE
 TOP OF THE HANDRAIL IS SPECIFIED AS 30" ON THE DETAIL.
 FBC-R 311.7.8.1 REQUIRES THIS DIMENSION TO BE NOT LESS
 THAN 34" NOR MORE THAN 38".
  
 2) THE LANDSCAPE AND DRAINAGE PLAN THAT WAS SUBMITTED
 DOES NOT SHOW COMPLIANCE WITH FBC-R 401.3 FOR SURFACE
 WATER DRAINAGE. SUBMIT TWO SETS OF SURFACE WATER
 DRAINAGE PLANS THAT SHOW COMPLIANCE WITH THE FOLLOWING:
 R401.3 DRAINAGE. SURFACE DRAINAGE SHALL BE DIVERTED TO
 A STORM SEWER CONVEYANCE OR OTHER APPROVED POINT OF
 COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS SHALL BE
 GRADED TO DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 INCHES (152
 MM) WITHIN THE FIRST 10 FEET (3048 MM).
 EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER
 PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL
 WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE
 CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE.
 IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE
 BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2
 PERCENT AWAY FROM THE BUILDING.
  
 3) NOTE #15 ON SHEET S-102, FOR DRAFTSTOPPING THE
 CONCEALED SPACES OF THE FLOOR/CEILING ASSEMBLY
 INCORRECTLY STATES THAT THE AREAS SHALL NOT EXCEED 100
 SF AND SECTION R 302.12 CODE STATES 1000 SF. PLEASE
 CORRECT.
  
 4) ON SHEET S-102, SPECIFY THE CONNECTORS THAT WILL BE
 USED TO ATTACH THE FLOOR TRUSSES TO THE LEDGERS IN
 ORDER TO RESIST LATERAL FORCES ON THE STRUCTURE. FBC
 107.2.1
  
 5) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD OF
 THE STRUCTURE. FBC 107.3.4
  
 6) THE INFORMATION THAT WAS SUBMITTED FOR THE BUILT-IN
 OUTDOOR BBQ DOES NOT HAVE THE LISTING INFORMATION OR
 INSTALLATION REQUIREMENTS, SUCH AS, CLEARANCES TO
 COMBUSTIBLES. SUBMIT ADDITION INFORMATION. FBC-R
 107.2.1
  
 7) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE ARCH
 TOP ENTRY DOORS AS REQUIRED BY FBC 107.3.4.
  
 8) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.