| 2017-05-24 11:07:51 | 2ND REVIEW: FBC 2014 5TH EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. S-503 SANITARY RISER DIAGRAM. |
| | A. THE WATER CLOSET AND BIDET IN THE MASTER BATHROOM |
| | ARE NOT VENTED PROPERLY. PER FBC RES P3101.2.1 |
| | B. THE SHOWER IN MASTER BATHROOM ARE NOT VENTED |
| | PROPERLY. PER FBC RES P3101.2.1 |
| | C. THE TWO BATHROOMS ON THE SECOND FLOOR RISER ARE NOT |
| | LABELED CORRECTLY BATH#5 IS LABELED AS LAUNDRY BATH #3 |
| | IS LABELED AS MASTERBATH PLEASE CLARIFY. PER WPB AMEND |
| | TO FBC 107.2.1 |
| | D. BATHROOM #4 IS MISSING ON THE SECOND FLOOR RISER |
| | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | E. THE VENT ON THE WATER CLOSET IN THE BATHROOM #5 IS |
| | NOT A REQUIRED VENTAND CAN NOT CONNECT TO-THE TOP OF |
| | THE WATER CLOSET RISER PLEASE REMOVE. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | 2. 2ND REQUEST A CLEAN OUT IS REQUIRED AT THE BASE OF |
| | ALL SOIL STACKS. PER FBC RES P3005.2.6 |
| | |
| | 3. PLEASE INCLUDE HOT WATER SYSTEM ON WATER RISER |
| | DIAGRAM. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | I SUGGEST TO EXPEDITE AN APPROVAL FOR PLUMBING THAT A |
| | MEETING BE SCHEDULED TO GO OVER THE COMMENTS ON THE |
| | RISER DIAGRAM. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |