Plan Review Notes For Permit 17030227
Permit Number 17030227
Review Stop P
Sequence Number 2
Notes
Date Text
2017-05-24 11:07:512ND REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. S-503 SANITARY RISER DIAGRAM.
 A. THE WATER CLOSET AND BIDET IN THE MASTER BATHROOM
 ARE NOT VENTED PROPERLY. PER FBC RES P3101.2.1
 B. THE SHOWER IN MASTER BATHROOM ARE NOT VENTED
 PROPERLY. PER FBC RES P3101.2.1
 C. THE TWO BATHROOMS ON THE SECOND FLOOR RISER ARE NOT
 LABELED CORRECTLY BATH#5 IS LABELED AS LAUNDRY BATH #3
 IS LABELED AS MASTERBATH PLEASE CLARIFY. PER WPB AMEND
 TO FBC 107.2.1
 D. BATHROOM #4 IS MISSING ON THE SECOND FLOOR RISER
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
 E. THE VENT ON THE WATER CLOSET IN THE BATHROOM #5 IS
 NOT A REQUIRED VENTAND CAN NOT CONNECT TO-THE TOP OF
 THE WATER CLOSET RISER PLEASE REMOVE. PER WPB AMEND TO
 FBC 107.2.1
  
 2. 2ND REQUEST A CLEAN OUT IS REQUIRED AT THE BASE OF
 ALL SOIL STACKS. PER FBC RES P3005.2.6
  
 3. PLEASE INCLUDE HOT WATER SYSTEM ON WATER RISER
 DIAGRAM. PER WPB AMEND TO FBC 107.2.1
  
 I SUGGEST TO EXPEDITE AN APPROVAL FOR PLUMBING THAT A
 MEETING BE SCHEDULED TO GO OVER THE COMMENTS ON THE
 RISER DIAGRAM.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  