2017-04-21 17:02:42DUE TO COMPUTER SYSTEM FAILURE, THIS IS ACTUALLY THE
 FIRST BUILDING PLAN REVIEW.
  
 PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE MEAN ROOF HEIGHT (MRH) IS INCORRECTLY SPECIFIED
 AS 15' ON SHEET S-000. THIS IS A TWO STORY STRUCTURE
 AND THE MEAN ROOF HEIGHT APPEARS TO BE APPROXIMATELY
 25'. FBC-R301.2.1
  
 2) PROVIDE COMPONENT AND CLADDING PRESSURES FOR ROOF
 ZONES 1, 2 & 3 AND WALL ZONES 4 & 5 ON THE PLANS. FBC
 107.3.5.3 - PROVIDE WIND DESIGN LOADS AND COMPONENT AND
 CLADDING DESIGN PRESSURES PURSUANT TO FBC-R301.2.
  
 3) SHOW COMPLIANCE WITH FBC-R 311.7 FOR STAIR
 REQUIREMENTS ON THE PLANS. STAIR DETAIL #10 ON S-300 IS
 FOR POURED CONCRETE STAIRS AND THE CODE REQUIREMENT
 INFORMATION IS NOT PROVIDED.
  
 4) SHOW COMPLIANCE WITH FBC-R 311.7.8 FOR HANDRAIL
 REQUIREMENTS ON THE PLANS.
  
 5) SHOW COMPLIANCE WITH FBC-R 312.1 FOR THE GUARDS
 REQUIRED AT THE BALCONY AND THE STAIRS ON THE PLANS.
  
 6) PROVIDE TWO SETS OF A SURFACE WATER DRAINAGE PLAN
 THAT SHOWS COMPLIANCE WITH FBC-R 401.3.
  
 7) THE SECOND FLOOR GAME ROOM HAS CLOSETS AND COULD BE
 USED AS A SLEEPING ROOM NOW OR IN THE FUTURE.
 THEREFORE, THE WINDOWS MUST COMPLY WITH FBC-R 310 FOR
 EMERGENCY ESCAPE AND RESCUE.
  
 8) SHOW COMPLIANCE WITH FBC-R 302.12 FOR DRAFTSTOPPING
 OF THE CONCEALED SPACE OF THE FLOOR / CEILING ASSEMBLY
 SO THAT THE AREA OF THE CONCEALED SPACE DOES NOT EXCEED
 1,000 SQUARE FEET.
  
 9) SHOW THE TRUSS TO LEDGER CONNECTORS ON SHEET S-102
 AND THE ROOF TO WALL CONNECTORS ON SHEET S-103. THERE
 ARE NO ID MARKS ON THE FLOOR AND ROOF FRAMING PLANS TO
 SHOW THE LOCATIONS OF THE CONNECTORS THAT ARE LISTED IN
 THE ANCHOR SCHEDULE ON SHEET S-400.
  
 10) THE OWNER/AGENT IS REQUIRED TO SIGN AND DATE THE
 ENERGY FORMS. TWO DIFFERENT ENERGY FORMS AND EQUIPMENT
 SIZING CALCULATIONS WERE SUBMITTED. PLEASE REMOVE THE
 OLD ONE AND SUBMIT AN ADDITIONAL COPY OF THE CORRECT
 ONE.
  
 11) FBC 107.3.4 - PROVIDE TWO SETS OF PRODUCT APPROVALS
 FOR THOSE PRODUCTS WHICH ARE REGULATED BY FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5) THAT HAVE
 BEEN REVIEWED AND APPROVED IN WRITING BY THE DESIGNER
 OF RECORD. PROVIDE TWO COMPLETE PRODUCT APPROVALS WITH
 FL OR NOA NUMBERS INCLUDING INSTALLATION INSTRUCTIONS
 AND MAXIMUM DESIGN PRESSURES FOR THE ARCH TOP ENTRY
 DOORS.
  
 12) PRODUCT APPROVALS WERE SUBMITTED FOR STRUCTURAL
 MULLIONS, HOWEVER, THE PLANS DO NOT APPEAR TO SHOW ANY
 MULLIONS. PLEASE CLARIFY. FBC 107.2.1
  
 13) SUBMIT TWO SETS OF THE EVALUATION REPORTS FOR THE
 ICYNENE SPRAY FOAM INSULATION. FBC-R 316
  
 14) SUBMIT TWO SETS OF THE MANUFACTURER?S
 SPECIFICATIONS AND LISTING INFORMATION FOR THE BUILT-IN
 OUTDOOR BBQ GRILL AND HOOD (IF ONE IS REQUIRED).
 FBC-R107.2.1
  
 15) SPECIFY THE MATERIAL THAT WILL BE INSTALLED ON THE
 CEILING OF THE SUMMER KITCHEN, LANAI AND COVERED ENTRY
 AREAS.
  
 16) IN ORDER TO REDUCE PLAN REVIEW TIME, PLEASE SUBMIT
 A RESPONSE LETTER INDICATING HOW EACH OF THE REVIEW
 COMMENTS HAS BEEN ADDRESSED.
  
  
  
  
  