| Notes |
| Date |
Text |
| 2017-03-17 12:56:51 | 1ST REVIEW | | | | | | GEORGE JOHNSON | | | PLUMBING PLANS EXAMINER LL | | | CITY OF WEST PALM BEACH | | | DEVELOPMENT SERVICES | | | BUILDING DIVISION | | | 561-805-6711 | | | [email protected] | | | | | | PLUMBING COMMENTS: | | | | | | 1. ON THE RISER THE WC IN MASTER BATHROOM IS NOT | | | VENTED. PER FBC PL P3101.2.1 | | | | | | 2. ON THE RISER THE LT IS NOT VENTED. PER FBC PL | | | P3101.2.1 | | | | | | 3. THE MASTER SH IS NOT SHOWN ON RISER PLEASE CLARIFY. | | | PER WPB AMEND TO FBC 107.2.1 | | | | | | 4. THE SOIL STACK FOR THE SECOND FLOOR IS NO SHOWN ON | | | THE GROUND FLOOR RISER PLEASE CLARIFY. PER WPB AMEND TO | | | FBC 107.2.1 | | | | | | 5. PLEASE PROVIDE A WATER RISER DIAGRAM. PER WPB AMEND | | | TO FBC 107.3.5.3(11) | | | | | | DUE TO THE DEFICIENCIES OF THIS PLAN A COMPLETE AND | | | THOROUGH REVIEW CANNOT BE DONE AT THIS TIME. UPON | | | RESUBMITTAL THERE MAYBE ADDITIONAL COMMENTS. | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | | |
|