| Plan Review Notes For Permit 17030227 |
| Permit Number |
17030227 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-04-18 13:58:46 | PASS PROVISO | | | 1) REFER TO SECTION M1301.3 PROVIDE MANUFACTURE | | | INSTALLATION INSTRUCTIONS | | | FOR RANGE HOOD AT FIRST INSPECTION. 2014 FBC(R) | | | 2) REFER TO SECTION M1602.4 BALANCED RETURN AIR. | | | REVISION REQUIRED | | | PROVIDE RETURN AIR FOR GAME ROOM 2014 FBC(R) | | | 3) PROVIDE A ENGINEER DETAIL ON THE CONDENSER TIE DOWN. | | | | | | PLAN REVIEW BY HAROLD MOSER | | | [email protected] | | | FAX 561-805-6676 | | | OFFICE 561-805-6732 | | | |
|