| Plan Review Notes For Permit 17030227 |
| Permit Number |
17030227 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-04-20 15:22:48 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC FIFTH EDITION (2014) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE MEAN ROOF HEIGHT (MRH) IS INCORRECTLY SPECIFIED | | | AS 15' ON SHEET S-000. THIS IS A TWO STORY STRUCTURE | | | AND THE MEAN ROOF HEIGHT APPEARS TO BE APPROXIMATELY | | | 25'. FBC-R301.2.1 | | | | | | 2) PROVIDE COMPONENT AND CLADDING PRESSURES FOR ROOF | | | ZONES 1, 2 & 3 AND WALL AREAS 4 & 5 ON THE PLANS. | | | FBC-R301.2.1 | | | | | | 3) SHOW COMPLIANCE WITH FBC-R 311.7 FOR STAIR | | | REQUIREMENTS ON THE PLANS. STAIR DETAIL #10 ON S-300 | | | ARE FOR POURED CONCRETE STAIRS AND ARE MISSING | | | INFORMATION. | | | | | | 4) SHOW COMPLIANCE WITH FBC-R 311.7.8 FOR HANDRAIL | | | REQUIREMENTS ON THE PLANS. | | | | | | 5) SHOW COMPLIANCE WITH FBC-R 312.1 FOR GUARDS | | | REQUIREMENTS AT THE BALCONY AND STAIR ON THE PLANS. | | | | | | 6) PROVIDE TWO SETS OF A SURFACE WATER DRAINAGE PLAN | | | THAT SHOWS COMPLIANCE WITH FBC-R401.3. | | | | | | 7) THE SECOND FLOOR GAME ROOM HAS CLOSETS AND COULD BE | | | USED AS A SLEEPING ROOM NOW OR IN THE FUTURE. THE | | | WINDOWS NEED TO COMPLY WITH FBC-R310 FOR EMERGENCY | | | ESCAPE ANE RESCUE. | | | | | | 8) **********************REVIEW NOT COMPLETE AT THIS | | | TIME******************** | | | | | | | | | |
|