2017-04-20 15:22:48PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE MEAN ROOF HEIGHT (MRH) IS INCORRECTLY SPECIFIED
 AS 15' ON SHEET S-000. THIS IS A TWO STORY STRUCTURE
 AND THE MEAN ROOF HEIGHT APPEARS TO BE APPROXIMATELY
 25'. FBC-R301.2.1
  
 2) PROVIDE COMPONENT AND CLADDING PRESSURES FOR ROOF
 ZONES 1, 2 & 3 AND WALL AREAS 4 & 5 ON THE PLANS.
 FBC-R301.2.1
  
 3) SHOW COMPLIANCE WITH FBC-R 311.7 FOR STAIR
 REQUIREMENTS ON THE PLANS. STAIR DETAIL #10 ON S-300
 ARE FOR POURED CONCRETE STAIRS AND ARE MISSING
 INFORMATION.
  
 4) SHOW COMPLIANCE WITH FBC-R 311.7.8 FOR HANDRAIL
 REQUIREMENTS ON THE PLANS.
  
 5) SHOW COMPLIANCE WITH FBC-R 312.1 FOR GUARDS
 REQUIREMENTS AT THE BALCONY AND STAIR ON THE PLANS.
  
 6) PROVIDE TWO SETS OF A SURFACE WATER DRAINAGE PLAN
 THAT SHOWS COMPLIANCE WITH FBC-R401.3.
  
 7) THE SECOND FLOOR GAME ROOM HAS CLOSETS AND COULD BE
 USED AS A SLEEPING ROOM NOW OR IN THE FUTURE. THE
 WINDOWS NEED TO COMPLY WITH FBC-R310 FOR EMERGENCY
 ESCAPE ANE RESCUE.
  
 8) **********************REVIEW NOT COMPLETE AT THIS
 TIME********************
  
  
  