| Plan Review Notes For Permit 17030213 |
| Permit Number |
17030213 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2017-06-13 04:41:02 | 1) SUBMIT A COMPLETE WATER AND SANITARY RISER DIAGRAM | | | FOR THE COMBINED UNIT "F".WPB AMEND. TO FBC SEC. | | | 107.3.5.1.3. | | | 2) SUBMIT A FLOOR PLAN SHOWING THE LOCATION OF "UNIT | | | F". I LOOKED AT ALL THE FLOOR PLANS SUBMITTED ON THE | | | ARCHITECTURAL SHEETS FOR THIS REVISION AND COULD NOT | | | FIND ONE THAT SHOWED THE LOCATION OF THIS UNIT.IT IS | | | VERY CONFUSING. WPB AMEND. TO FBC SEC. 107.2.1.WHAT | | | UNITS/AREAS WERE COMBINED TO FORM UNIT F? INDICATE ON | | | THE ENLARGED PLANS FOR UNIT F. WPB AMEND. TO FBC SEC. | | | 107.2.1. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | | | | |
|