| 2017-03-09 09:46:56 | 1ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING | | | PERMIT #17030212 | | | 3/9/17 | | | | | | 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE | | | AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL | | | ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED CFMS OF OUTDOOR AIR. | | | | | | 2) SHEET M-2: PROVIDE THE CFMS AT EACH SUPPLY DIFFUSER | | | AND RETURN GRILL- SECTION C403.2.7.5 FBC-14 ENERGY | | | CONSERVATION. PLEASE NOTE THAT TESTING BALANCING IS | | | REQUIRED PER SECTION C408.2.2. | | | | | | 3) M-2. KEY NOTE #13: IT APPEARS THAT AIR IS BEING | | | TRANSFERRRED INTO THE EGRESS CORRIDOR WHICH IS NOT | | | PERMITTED PER SECTION 601.2. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|