2017-03-09 09:46:561ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING
 PERMIT #17030212
 3/9/17
  
 1) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 2) SHEET M-2: PROVIDE THE CFMS AT EACH SUPPLY DIFFUSER
 AND RETURN GRILL- SECTION C403.2.7.5 FBC-14 ENERGY
 CONSERVATION. PLEASE NOTE THAT TESTING BALANCING IS
 REQUIRED PER SECTION C408.2.2.
  
 3) M-2. KEY NOTE #13: IT APPEARS THAT AIR IS BEING
 TRANSFERRRED INTO THE EGRESS CORRIDOR WHICH IS NOT
 PERMITTED PER SECTION 601.2.
  