2017-03-09 15:44:40846 SOUTHERN BOULEVARD
 PERMIT #17030212
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 NO ADDRESS OR SUITE NUMBER PROVIDED ON THE PLANS.
  
 PLANS STATE THE BUILDING IS PROTECTED BY AUTOMATIC
 SPRINKLERS; HOWEVER, NO SPRINKLER RENOVATION SCOPE IS
 SHOWN ON THE PLANS.
  
 PROVIDE A STORAGE ROOM LAYOUT TO ENSURE DEDICATED
 EGRESS ROUTES CAN AND WILL BE MAINTAINED.
  
 NO ROOM NAME OR OCCUPANCY LISTED ADJACENT TO THE
 RESTROOM. WHY IS A DOOR FROM AN ADJACENT TENANT SPACE
 LOCATED IN THIS WALL?
  
 NO EXIT SIGN PROVIDED ON EMPLOYEE SIDE OF NEW DOOR
 SEPARATING SUPPLY ROOM FROM SALES AREA.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL