Plan Review Notes
Plan Review Notes For Permit 17030212
Permit Number 17030212
Review Stop E
Sequence Number 1
Notes
Date Text
2017-03-14 09:24:09INITIAL ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION FOR ALL LOW VOLTAGE
 SYSTEMS TO INCLUDE BUT NOT LIMITED TO CCTV, PHONE AND
 DATA, WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE.
 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3,
 405.7.4 SEE VERBIAGE IN THE CODE REGARDING VOLTAGE DROP
 FOR FEEDERS AND BRANCH CIRCUITS AND COMPLETIONS
 DOCUMENTS.
 3. PLEASE PROVIDE INTERIOR LIGHTING LEVELS AS REQUIRED
 BY FBC EC 405.
 4. SHOW GFCI BREAKER AT PANEL BOARD FOR DRINKING
 FOUNTAIN, AS GFCI WILL NEED TO BE READILY ACCESSIBLE
 PER NEC 210.8B.
 5. COULD NOT LOCATE SIGN RECEPTACLE AND LOAD AT PANEL
 SCHEDULE AS REQUIRED PER NEC 600.5A
 6. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE
 TO CONTACT ME SHOULD YOU HAVE ANY
  
  