| Plan Review Notes For Permit 17030212 |
| Permit Number |
17030212 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2017-03-14 09:24:09 | INITIAL ELECTRICAL PLAN REVIEW | | | | | | APPLICABLE CODES IN EFFECT: | | | FLORIDA BUILDING CODE 2014 5TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | | EDITION | | | NFPA 70- 2011 | | | COMMENTS: | | | | | | 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE | | | PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE | | | PERMITS AND DATA SPECIFICATION FOR ALL LOW VOLTAGE | | | SYSTEMS TO INCLUDE BUT NOT LIMITED TO CCTV, PHONE AND | | | DATA, WIRELESS SYSTEMS, ETC. A NOTE WILL SUFFICE. | | | 2. PROVIDE A SHOW COMPLIANCE WITH FBC EC 405.7.3, | | | 405.7.4 SEE VERBIAGE IN THE CODE REGARDING VOLTAGE DROP | | | FOR FEEDERS AND BRANCH CIRCUITS AND COMPLETIONS | | | DOCUMENTS. | | | 3. PLEASE PROVIDE INTERIOR LIGHTING LEVELS AS REQUIRED | | | BY FBC EC 405. | | | 4. SHOW GFCI BREAKER AT PANEL BOARD FOR DRINKING | | | FOUNTAIN, AS GFCI WILL NEED TO BE READILY ACCESSIBLE | | | PER NEC 210.8B. | | | 5. COULD NOT LOCATE SIGN RECEPTACLE AND LOAD AT PANEL | | | SCHEDULE AS REQUIRED PER NEC 600.5A | | | 6. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL FREE | | | TO CONTACT ME SHOULD YOU HAVE ANY | | | | | | | | | VALENTINO PEREZ | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6717 | | | [email protected] | | | | | | | | | | | | |
|